6.1 Programming the 635-Model CPU Board via Web Page
This subsection provides quick steps for programming the CPU from the embedded web page. The CPU comes from
the factory with a default
192
… IP Address. You can identify each CPU by its serial number.
SEE CHAPTER-1 FOR A FULL LIST OF IT REQUIREMENTS
•
Specific port numbers must be available and not blocked by firewalls, switches, or routers.
System
Galaxy uses port numbers 1433, 5010, 3001, 4000, 4001, 4002, and 4003
.
•
Windows OS
need to set PC firewall at the Communication Server to accept the File and Print Sharing,
sqlservr.exe and sqlbrowser.exe.
•
635 Controller: TCP/IP over LAN/WAN 10/100 Mb Ethernet/Full Duplex at port side.
•
Unique, IP Addresses must be given to each Galaxy Panel (CPU)
and the computers that host the GCS
Communication and Event Services.
If private IP Addresses are not available, a non-routable IP Address should be used.
NOTICE: If DHCP addressing is used, and the DHCP server goes offline or changes the addresses, then
connectivity between the server and loops will be adversely affected!
1.
Install the 635 Web Configuration Tool
on a PC that is connected to the same broadcast domain as the 635
panel/s you wish to program or test.
2.
Click desktop icon
to start the Web Tool (your default browser opens).
3.
If dual NIC cards are used, select the correct NIC card in the droplist.
Figure 43 – Example of 635 Web Config Tool Screen