224
Upgrade and Maintenance Manual
TX2560 M2 / RX2560 M2
Hard disk drive (HDD) / solid state drive (SSD)
Ê
"Removing the system air duct" on page 91
Ê
"Removing the system fan holder" on page 93
Ê
Disconnect all cables from the defective SAS backplane.
7.3.12.2 Removing the 3.5-inch HDD bay top cover
I
The 3.5-inch HDD front panel does not need to be removed in order to
replace a 3.5-inch HDD SAS backplane. In the figures, the front panel
has been removed for illustration purposes only.
Figure 136: Removing the 3.5-inch HDD bay top cover (A)
Ê
Remove five screws from the 3.5-inch HDD bay top cover (see blue circles).
Ê
Remove one screw from the intrusion switch holder (see orange circle).