TX2560 M2 / RX2560 M2
Upgrade and Maintenance Manual
481
System board and components
14.6.3.2 Replacing the iRMC microSD card
Ê
Remove the defective iRMC microSD card as described in section
"Removing the iRMC microSD card" on page 479
.
V
CAUTION!
The iRMC microSD card contains customer information. After
replacing the iRMC microSD card, hand the defective card over to the
customer. If the customer requests disposal of the defective iRMC
microSD card, proceed as follows:
Ê
Using a pair of side-cutting pliers, cut the iRMC microSD card in
half.
Ê
Install the new iRMC microSD card as described in section
iRMC microSD card" on page 477
.
14.6.3.3 Concluding steps
Ê
If applicable, install the riser module 2 as described in section
Ê
Ê
"Connecting the power cord" on page 87
Ê
Summary of Contents for PRIMERGY RX2560 M2
Page 6: ...Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 ...
Page 26: ...Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Contents ...
Page 42: ...42 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Before you start ...
Page 110: ...110 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Basic hardware procedures ...
Page 152: ...152 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Power supply unit PSU ...
Page 364: ...364 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Main memory ...
Page 434: ...434 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Accessible drives ...
Page 492: ...492 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 System board and components ...
Page 544: ...544 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Cabling ...
Page 568: ...568 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Appendix ...