TX2560 M2 / RX2560 M2
Upgrade and Maintenance Manual
221
Hard disk drive (HDD) / solid state drive (SSD)
For further information, please refer to the "ServerView Suite RAID
Management" user guide.
Ê
When working on a tower server, open the HDD bay cover as described in
section
"Removing accessible drive and HDD bay covers" on page 71
.
7.3.10.2 Removing a 3.5-inch HDD module
Ê
Pinch the green locking clips and open the locking lever (see
Ê
Pull the HDD module out a few centimeters.
Ê
Wait about 30 seconds to allow the HDD to spin down.
I
This period is necessary for the RAID controller to recognize that an
HDD module has been removed and for the HDD to come to a stop.
Ê
Pull the HDD module completely out of its bay.
7.3.10.3 Installing a 3.5-inch HDD dummy module
V
CAUTION!
If the removed HDD module is not replaced immediately, always replace
a dummy module into the unused HDD bay to comply with applicable
EMC regulations and satisfy cooling requirements.
Figure 135: Installing a 3.5-inch HDD dummy module
Ê
Push the dummy module into the empty bay until it engages.
Summary of Contents for PRIMERGY RX2560 M2
Page 6: ...Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 ...
Page 26: ...Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Contents ...
Page 42: ...42 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Before you start ...
Page 110: ...110 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Basic hardware procedures ...
Page 152: ...152 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Power supply unit PSU ...
Page 364: ...364 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Main memory ...
Page 434: ...434 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Accessible drives ...
Page 492: ...492 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 System board and components ...
Page 544: ...544 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Cabling ...
Page 568: ...568 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Appendix ...