2-6. Medium static pressure duct type
Model name
ARUM24TLAV2
ARUM30TLAV2
ARUM36TLAV2
Power supply
1 phase ~ 208/230 V 60 Hz
Available voltage range
187—253 V
Capacity
Cooling
Btu/h
24,000
30,000
36,000
kW
7.0
8.8
10.6
Heating
Btu/h
27,000
34,000
40,000
kW
7.9
10.0
11.7
Input power
W
125
190
222
Static pressure range
inWG (Pa)
0 to 0.60 (0 to 150)
Standard static pressure
inWG (Pa)
0.16 (40)
Fan
Airflow rate
HIGH
CFM (m
3
/h)
860 (1,460)
1,043 (1,770)
1,113 (1,890)
MED—HIGH
807 (1,370)
948 (1,610)
1,031 (1,750)
MED
760 (1,290)
860 (1,460)
954 (1,620)
MED—LOW
701 (1,190)
772 (1,310)
854 (1,450)
LOW
648 (1,100)
683 (1,160)
766 (1,300)
QUIET
589 (1,000)
589 (1,000)
677 (1,150)
Type × Q'ty
Sirocco × 2
Motor output
W
197
Sound pressure level*
HIGH
dB (A)
36
40
41
MED—HIGH
34
37
39
MED
32
34
37
MED—LOW
30
32
34
LOW
29
30
31
QUIET
28
28
29
Heat exchanger type
Length
in (mm)
39-3/8 (1,000)
Fin pitch
FPI
18
Rows × Stages
4 × 14
Face area
ft
2
(m
2
)
3.1 (0.29)
Pipe type (Material)
Grooved H-pin (Copper)
Fin
Type (Material)
Slit (Aluminum)
Surface treatment
Hydrophilic coating
Air filter (Option)
Model name
UTD-LF25NA
Type
Fungicide type
Net material
PP honeycomb
Enclosure
Material
Galvanized sheet iron
Color
—
Dimensions
(H × W × D)
Net
in (mm)
10-5/16 × 44-11/16 × 27-9/16 (270 × 1,135 × 700)
Gross
11-13/16 × 51-15/16 × 31-1/8 (300 × 1,320 × 790)
Weight
Net
lb (kg)
86 (39)
Gross
104 (47)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 3/8 (9.52)
Gas (Flare)
Ø 5/8 (15.88)
Drain hose
I.D.: Ø 3/4 (19.05); O.D.: Ø 1-1/16 (26.6)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
– Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-6. Medium static pressure duct type
- (04-13) -
2. Specifications
INDOOR
UNITS
INDOOR
UNITS
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...