Model name
ARUL18TLAV2
Power supply
1 phase ~ 208/230 V 60 Hz
Available voltage range
187—253 V
Capacity
Cooling
Btu/h
18,000
kW
5.3
Heating
Btu/h
20,000
kW
5.9
Input power
W
83
Static pressure range
inWG (Pa)
0 to 0.36 (0 to 90)
Standard static pressure
inWG (Pa)
0.10 (25)
Fan
Airflow rate
HIGH
CFM (m
3
/h)
554 (940)
MED—HIGH
483 (820)
MED
430 (730)
MED—LOW
371 (630)
LOW
318 (540)
QUIET
277 (470)
Type × Q'ty
Sirocco × 3
Motor output
W
81
Sound pressure level*
HIGH
dB (A)
34
MED—HIGH
31
MED
29
MED—LOW
27
LOW
25
QUIET
23
Heat exchanger type
Length
in (mm)
27-9/16 (700)
Fin pitch
FPI
19
Rows × Stages
3 × 14
Face area
ft
2
(m
2
)
2.3 (0.21)
Pipe type (Material)
Grooved H-pin (Copper)
Fin
Type (Material)
Slit (Aluminum)
Surface treatment
Hydrophilic coating
Air filter
Type
Fungicide type
Net material
PP honeycomb
Enclosure
Material
Galvanized sheet iron
Color
—
Dimensions
(H × W × D)
Net
in (mm)
7-13/16 × 35-7/16 × 24-7/16 (198 × 900 × 620)
Gross
10-7/8 × 46 × 30-3/8 (276 × 1,168 × 772)
Weight
Net
lb (kg)
49 (22)
Gross
60 (27)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 1/4 (6.35)
Gas (Flare)
Ø 1/2 (12.70)
Drain hose
VP25
I.D.: Ø 3/4 (19.05); O.D.: Ø 1-1/16 (26.6)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
– Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-5. Slim duct/Slim concealed floor type
- (04-12) -
2. Specifications
INDOOR
UNITS
INDOOR
UNITS
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...