• When electricity meter used is specified by pulse constant
The connection configuration is shown below.
For the electricity meter specified by pulse constant, the power consumption indicated by output
pulse must be corrected by VT/CT ratio. In this case, the settings are as follows:
Set point
Set item
Set value
Description
Remarks
Electricity
meter
Set in accordance
with the product
manual.
—
When there is a product unique
setting, setting is performed in
accordance with the product
manual. (Pulse constant value,
output coefficient, etc.)
Outdoor
unit
Meter no. setting
Arbitrary
Set an unique electricity meter no.
for electricity meter identification.
The information will
become necessary
when setting
System controller
later. Refer also to
Electricity meter
pulse setting
The pulse
constant value /
(VT ratio × CT
ratio). However,
truncated after
the decimal point
Set the approximate number of
power meter pulses that are
equivalent to 1kWh.
When set number of pulses come
from the electricity meter, the
outdoor unit communicates “1” to
the system controller.
System
controller
Electricity meter
system setting
Units measured
by electricity
meter
Set the outdoor unit and indoor
unit, measured by the electricity
meter of the meter no. set at the
outdoor unit.
The value set by
each outdoor unit is
used.
Pulse setting
(Electricity meter
pulse setting
value) × (VT ratio
× CT ratio) /
pulse constant
Values after the
decimal point
must be also
input.*
Set the standard number of kWh for
the value communicated from the
outdoor unit.
Set the number of kWh that
corresponds to the “1”
communicated from the outdoor
unit.
Refer to the value
set by each outdoor
unit.
*: Input up to 6 decimal digits
[Setting example]
Equipment conditions:
VT ratio=1 (not used), CT ratio=500(2500/5 A), electricity meter=3,200 pulse/kWh
Set value:
Electricity meter pulse setting=6 (3200/ [1 × 500]), Pulse setting=0.9375 (6 × [1 × 500]/3200) For
details, refer to the calculating formula of the table above.
2-26. Electricity charge apportionment setting (System controller, Touch panel
controller)
- (07-151) -
2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...