6.
When the automatic address setting is completed, the number of indoor units of which the auto-
matic address setting succeeded is displayed on the LED105, and the number of indoor units of
which the automatic address setting failed is displayed on the LED104.
Example: When 25 indoor units are connected, and the automatic
setting of the addresses of all indoor units ended normally
LED105
LED104
LED105
LED104
(Setting completed)
LED105: The number of indoor units of
which automatic address setting succeeded
LED104: The number of indoor units of
which automatic address setting failed
Example: When 25 indoor units are connected, and the automatic
setting of the addresses of three indoor units failed
LED105
LED104
LED105
LED104
LED105: The number of indoor units of
which automatic address setting succeeded
LED104: The number of indoor units of
which automatic address setting failed
If automatic address setting failed, make sure that all of the rotary switches SW6 to SW9 on the
PCBs of the failed indoor units are positioned at “0” and that wiring and power supply are cor-
rect, and then perform the automatic address setting again.
7.
When the ENTER button (SW109) is pressed, end processing will begin and the LED displays
start to blink. For completing this process will take about 30 seconds.
LED105
LED104
LED105
LED104
LED105
LED104
When the setting is completed, the LED displays go off.
1-5. Automatic address setting
- (07-53) -
1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...