CAUTION
•
Brazing:
– If nitrogen gas is not blown through the pipes while they are being brazed, an oxidized layer
may form on the inside of the pipes. If this occurs, the cooling efficiency may decrease and it
will be caused to damage for compressor and clog the strainer and electronic expansion
valve.
Example: Inside state of brazing pipe section
Nitrogen gas used
Nitrogen gas used but not sufficient
(Oxigen gas still inside the pipe)
Nitrogen gas does not used
– When brazing the pipes, do not use flux. If the flux is chlorine-based, the pipes will corrode
and when the flux contains fluorine, the refrigerant oil will deteriorate, etc. Using the flux has
an adverse affect on the refrigerant piping system.
– For brazing materials, use phosphor copper solder that does not require flux.
- (06-36) -
3. Piping connection
SYSTEM
DESIGN
SYSTEM
DESIGN
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...