Address setting by simple remote controller (UTY-RSKU and
UTY-RHKU)
• Indoor unit addresses and refrigerant circuit addresses can be set up using wired remote con-
trollers.
• This function allows setting the addresses of all indoor units to which a wired remote controller is
being connected.
• This function cannot be used to set up remote controller addresses.
Be sure to set them up using the rotary switches on the PCB of each indoor unit. (Refer to
• This function cannot be used on the slave units.
• This function can be set up on both UTY-RSKU (with operation mode) and UTY-RHKU (without
operation mode) types.
Preparation
1.
Make sure that all indoor unit address switches (IU AD x10, IU AD x1) and refrigerant circuit
address switches (REF AD x10, REF AD x1) on the PCB of each indoor unit are set at 0 (facto-
ry setting).
The layout of the switches differs by the type of the indoor unit. For the details, refer to
Rotary switch
(type A)
SW601
SW602
SW604 SW605
SW606 SW607 SW608
Check the switch position is set at “0”.
(Factory setting)
IU AD x10
IU AD x1
REF AD x10
REF AD x1
2.
If multiple indoor units are connected to a single simple remote controller, set up the remote
controller address (RC AD) manually on the indoor units PCBs by referring
0
1
2
3
Indoor unit
Indoor unit
Indoor unit
Indoor unit
RC AD
RC AD
RC AD
RC AD
Simple remote controller
Example: When 4 indoor units are connected
3.
Before turning on the power of indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
4.
Turn on the power of indoor units.
By turning on the power, the indoor units initialize EEV.
Indoor units
Indoor units
Breaker ON
1-4. Address setting by remote controller
- (07-38) -
1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...