Simple procedure for create XIF and register data to Network
convertor for LonWorks
Important
Network convertor will not operate if,
• VRF network system address (Outdoor and Indoor units address) allocation information are not
registered to Network convertor.
• XIF data information and VRF network system address allocation information must not be the
same.
• Binding and commissioning are not executed. (During binding, read out the Network convertor
Neuron ID by pushing BMS service switch [SW2] on the main PCB of Network convertor.)
• If the ID number registered to the Network convertor is not same as the ID number which is in-
cluded in the XIF of Network convertor.
NOTE:
For detailed information, refer to the application manual which is included inside packaged
CD-ROM.
The following is the on-line procedure. It is also possible to create XIF and register data off-line.
1.
Connect the PC and this product.
Connection will be done by the connector cable provided as an accessory item of this product.
2.
Install tool for convertor (software) in PC.
Tool for convertor is the accessory item of this product.
3.
Set this product to installation mode.
4.
Setting ID number of this product on PC screen of tool for convertor.
(ID number is required to identify this product from BMS. A maximum number of four Network
convertors can be connected to one BMS, and ID number allocation is like 00, 01, and so on.)
5.
Initial setting of indoor unit and outdoor unit address by using the tool for convertor.
6.
Register the initial setting data to this product. Click “Register” dialog.
7.
Set configuration properties.
To set the communication properties of this product, select the following communication proper-
ties and types; otherwise, the default value will be used.
• Select communication items
– Event driven communication or Cyclic communication (Default: Cyclic 3 minutes)
– Communication interval time during turning on all together (Default: 3 minutes)
• Select communication type (to communicate data with BMS)
– Communicate only when changing network variable or communicate all network variable.
(Default: Only when changing network variable)
– Communicate only when changing room temperature value (Default: Room temperature
changed value 1.8 °F [1 °C])
8.
Register the configuration properties data to this product. Click the “Register” dialog.
9.
Creating/Modifying XIF, and transfer XIF data by USB memory or floppy disk for binding.
10.
Press “Reset SW7” to reset this product.
11.
Turn off the power. After that, remove the connection of PC and this product respectively.
In this stage, Network convertor is ready for binding and commissioning.
3-3. Network convertor for LonWorks (UTY-VLGX)
- (05-128) -
3. Adaptor/Convertor units
CONTROL
SYSTEM
CONTROL
SYSTEM
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...