[Function setting of indoor unit]
Indoor unit continues appropriate operation until Forced thermostat off signal is received, at condi-
tion which are set by central and individual controller or detected by thermo sensors of the indoor
unit. Once the Forced thermostat off signal is received, the indoor unit start operation under fan
mode.
49
00
Indoor unit
Function
no.
Set setting no. 49-00
Setting
no.
[Example of electrical circuit]
1
2
3
4
5
6
1
2
CNA04
Indoor unit
Service parts
Relay
External
controller
Indoor unit
PCB
Max. 492 ft (150 m)
Dry contact
external input wire
CNB01
Specification of external input
Item
Specification
Terminal
CNA04
Output voltage
DC 12 V
Wire diameter
22 AWG (0.33 mm
2
), Twisted
Service part no.
9368778019
Requirement for relay switch
Item
Specification
Minimum permissible load
1 mA or less
3-2. External input
- (08-19) -
3. Indoor unit
EXTERNAL INPUT
AND OUTPUT
EXTERNAL INPUT
AND OUTPUT
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...