LED105
code no.
Setting mode
LED104
code no.
Setting function
Factory
setting
Remarks
3
6
Outdoor
temperature
zone boundary
temperature A
0
0
-4.0 °F (-20 °C)
♦
Setting if changing the outdoor
temperature setting for heat pump
prohibition zone is required when
heater selection control using
outdoor temperature 1 and 2 are
performed on indoor unit.
For details, refer to
INPUT AND OUTPUT on page 08-
5.
0
1
-0.4 °F (-18 °C)
0
2
3.2 °F (-16 °C)
0
3
6.8 °F (-14 °C)
0
4
10.4 °F (-12 °C)
0
5
14.0 °F (-10 °C)
0
6
17.6 °F (-8 °C)
0
7
21.2 °F (-6 °C)
0
8
24.8 °F (-4 °C)
3
7
Outdoor
temperature
zone boundary
temperature B
0
0
42.8 °F (6 °C)
♦
Setting if changing the outdoor
temperature setting for heat pump
only zone is required when heater
selection control using outdoor
temperature 1 is performed on
indoor unit.
For details, refer to
INPUT AND OUTPUT on page 08-
5.
0
1
14.0 °F (-10 °C)
0
2
17.6 °F (-8 °C)
0
3
21.2 °F (-6 °C)
0
4
24.8 °F (-4 °C)
0
5
28.4 °F (-2 °C)
0
6
32.0 °F (-0 °C)
0
7
35.6 °F (2 °C)
0
8
39.2 °F (4 °C)
0
9
42.8 °F (6 °C)
1
0
46.4 °F (8 °C)
1
1
50.0 °F (10 °C)
1
2
53.6 °F (12 °C)
1
3
57.2 °F (14 °C)
1
4
60.8 °F (16 °C)
1
5
64.4 °F (18 °C)
4
0
Capacity
priority setting
(in low noise
mode)
0
0
Off (Quiet priority)
♦
If the cooling/heating performance
becomes insufficient when the low
noise mode is set, it is possible to
set “Capacity priority” that
automatically cancels the low
noise mode. (Once performance is
restored, the mode will
automatically return to the low
noise mode.)
0
1
On (Capacity priority)
4
1
Low noise
mode setting
0
0
Off (Normal)
♦
0
1
On (Low noise mode)
4
2
Low noise
mode operation
level setting
0
0
Level 1
♦
Level 1: The operating sound
lowers from about 3 to 5 dB (A)
more than the rated value.
0
1
Level 2
Level 2: The operating sound
lowers from about 3 to 5 dB (A)
more than the Level 1.
6
0
Prohibited
0
0
Prohibited
♦
Setting prohibited
0
1
Prohibited
7
0
Electricity
meter no.
setting 1 *
1
0
0
Setting number x00
♦
Set the ones digit and tens digit of
the number of the electricity meter
connected to CN135.
0
1
Setting number x01
•
•
•
•
•
•
•
•
•
9
8
Setting number x98
9
9
Setting number x99
7
1
Electricity
meter no.
setting 2 *
1
0
0
Setting number 0xx
♦
Set the hundreds digit of the
number of the electricity meter
connected to CN135.
0
1
Setting number 1xx
0
2
Setting number 2xx
2-1. Setting on outdoor unit PCB
- (07-65) -
2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...