Model name
AUUB30TLAV
AUUB36TLAV
Power supply
1 phase ~ 208/230 V 60 Hz
Available voltage range
187—253 V
Capacity
Cooling
Btu/h
30,000
36,000
kW
8.8
10.6
Heating
Btu/h
34,000
40,000
kW
10.0
11.7
Input power
W
59
80
Fan
Airflow rate
HIGH
CFM (m
3
/h)
942 (1,600)
1,059 (1,800)
MED
765 (1,300)
765 (1,300)
LOW
647 (1,100)
647 (1,100)
Type × Q'ty
Turbo × 1
Motor output
W
80
Sound pressure level*
HIGH
dB (A)
40
44
MED
38
38
LOW
33
33
Heat exchanger type
Length
in (mm)
81-15/16 (2,082)
Fin pitch
FPI
19
Rows × Stages
3 × 12
Face area
ft
2
(m
2
)
5.6 (0.52)
Pipe type (Material)
Grooved H-pin (Copper)
Fin
Type (Material)
Slit (Aluminum)
Surface treatment
Hydrophilic coating
Air filter
Type
Anti-mold
Net material
PP honeycomb
Enclosure
Material
Galvanized sheet iron
Color
—
Dimensions
(H × W × D)
Net
Main body
in (mm)
11-5/16 × 33-1/16 × 33-1/16 (288 × 840 × 840)
Gross
14-3/16 × 37-13/16 × 38-9/16 (360 × 960 × 980)
Weight
Net
lb (kg)
60 (27)
Gross
73 (33)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 3/8 (9.52)
Gas (Flare)
Ø 5/8 (15.88)
Drain hose
VP25
I.D.: Ø 3/4 (19.05); O.D.: Ø 1-1/16 (26.6)
Cassette grille
(Option)
Model name
UTG-LCGV
Color
WhiteApproximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
in (mm)
1-15/16 × 37-3/8 × 37-3/8 (50 × 950 × 950)
Gross
4-1/2 × 40-3/16 × 39-3/8 (115 × 1,020 × 1,000)
Weight
Net
lb (kg)
13 (5.5)
Gross
19 (8.5)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
– Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-3. Cassette type
- (04-9) -
2. Specifications
INDOOR
UNITS
INDOOR
UNITS
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...