Base heater
This is the output signal for base heater.
The output signal is on when the outdoor temperature goes down below 36°F (2°C), and signal is off
at the outdoor temperature 39°F (4°C).
1
2
3
4
CN115
(Black)
Voltage: Power supply
input voltage
Base heater *
2
*
1
PCB
18 AWG (0.82 mm
2
)
*
1
:
Connect to pin no.1 and pin no.3. No connection to pin no.2 and pin no.4.
*
2
:
The allowable current is 1 A or less.
2-5. Optional parts
External connect kit
Model name
Exterior
Q’ty
Usage
UTY-XWZXZ6
1
For external input.
(Low noise mode, Cooling/Heating priority,
Outdoor unit operation peak control, Emergency/
Batch stop)
For external output.
(Error status, Operation status)
UTY-XWZXZ9
1
For external output.
(Base heater)
UTY-XWZXZF
1
For external input.
(Electricity meter pulse)
2-4. External output
- (08-6) -
2. Outdoor unit
EXTERNAL INPUT
AND OUTPUT
EXTERNAL INPUT
AND OUTPUT
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...