Function
Function
number
Setting number
Factory
setting
Details
External
heater use
in defrosting
75
00
Disabled
♦
Enables or disables the external heater use in
defrosting.
NOTE:
When using function number 75,
inappropriate heater selection may cause
cold air in defrosting.
01
Enabled
Range of static pressure mode by model
Model name
Range of static pressure mode
Normal static pressure
ARUL4TLAV1
SP mode 00 to 03
0.04 inWG (10 Pa)
ARUL7TLAV2
SP mode 00 to 09
0.10 inWG (25 Pa)
ARUL9TLAV2
ARUL12TLAV2
ARUL14TLAV2
ARUL18TLAV2
ARUM24TLAV2
SP mode 00 to 14
0.16 inWG (40 Pa)
ARUM30TLAV2
SP mode 00 to 11
ARUM36TLAV2
SP mode 00 to 09
ARUH36TLAV
Setting prohibited
because of AC motor
0.40 inWG (100 Pa)
ARUH48TLAV
ARUH60TLAV
ARUH72TLAV2
SP mode 05 to 30
0.60 inWG (150 Pa)
ARUH96TLAV2
SP mode 05 to 29
Temperature conditions when the external heater is on/off
Temperature (t) = Room temperature - set temperature
Set value of function: 61
00
01 to 99
External heater: On
External heater: Off
External heater: On
External heater: Off
Set value
of
function:
62
00
t < -5.4 °F (-3 °C)
t ≥ -1.8 °F (-1 °C)
t ≤ -0.9 °F (-0.5 °C)
t ≥ 0.9 °F (0.5 °C)
01
t < -3.6 °F (-2 °C)
t ≥ -1.8 °F (-1 °C)
t ≤ -1.8 °F (-1 °C)
t ≥ 0.9 °F (0.5 °C)
02
t < -3.6 °F (-2 °C)
t ≥ -1.8 °F (-1 °C)
t ≤ -3.6 °F (-2 °C)
t ≥ 0.9 °F (0.5 °C)
03
t < -5.4 °F (-3 °C)
t ≥ -1.8 °F (-1 °C)
t ≤ -5.4 °F (-3 °C)
t ≥ 0.9 °F (0.5 °C)
04
t < -7.2 °F (-4 °C)
t ≥ -1.8 °F (-1 °C)
t ≤ -7.2 °F (-4 °C)
t ≥ 0.9 °F (0.5 °C)
05
t < -9.0 °F (-5 °C)
t ≥ -1.8 °F (-1 °C)
t < -9.0 °F (-5 °C)
t ≥ 0.9 °F (0.5 °C)
06
t < -5.4 °F (-3 °C)
t ≥ -0.9 °F (-0.5 °C)
t ≤ -0.9 °F (-0.5 °C)
t ≥ 0 °F (0 °C)
07
t < -3.6 °F (-2 °C)
t ≥ -0.9 °F (-0.5 °C)
t ≤ -1.8 °F (-1 °C)
t ≥ 0 °F (0 °C)
08
t < -3.6 °F (-2 °C)
t ≥ -0.9 °F (-0.5 °C)
t ≤ -3.6 °F (-2 °C)
t ≥ 0 °F (0 °C)
09
t < -5.4 °F (-3 °C)
t ≥ -0.9 °F (-0.5 °C)
t ≤ -5.4 °F (-3 °C)
t ≥ 0 °F (0 °C)
10
t < -7.2 °F (-4 °C)
t ≥ -0.9 °F (-0.5 °C)
t ≤ -7.2 °F (-4 °C)
t ≥ 0 °F (0 °C)
11
t < -9.0 °F (-5 °C)
t ≥ -0.9 °F (-0.5 °C)
t < -9.0 °F (-5 °C)
t ≥ 0 °F (0 °C)
12
t < -5.4 °F (-3 °C)
t ≥ 0 °F (0 °C)
t ≤ -0.9 °F (-0.5 °C)
t ≥ -0.9 °F (-0.5 °C)
13
t < -3.6 °F (-2 °C)
t ≥ 0 °F (0 °C)
t ≤ -1.8 °F (-1 °C)
t ≥ -0.9 °F (-0.5 °C)
14
t < -3.6 °F (-2 °C)
t ≥ 0 °F (0 °C)
t ≤ -3.6 °F (-2 °C)
t ≥ -0.9 °F (-0.5 °C)
15
t < -5.4 °F (-3 °C)
t ≥ 0 °F (0 °C)
t ≤ -5.4 °F (-3 °C)
t ≥ -0.9 °F (-0.5 °C)
16
t < -7.2 °F (-4 °C)
t ≥ 0 °F (0 °C)
t ≤ -7.2 °F (-4 °C)
t ≥ -0.9 °F (-0.5 °C)
17
t < -9.0 °F (-5 °C)
t ≥ 0 °F (0 °C)
t < -9.0 °F (-5 °C)
t ≥ -0.9 °F (-0.5 °C)
2-9. Function details
- (07-100) -
2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...