CEILING TYPE
3-4.
Type
CEILING MODEL
INVERTER HEATPUMP
Model name
AB
G36LRTA
AB
G45LRTA
AB
G54LRTA
Power source
3N~ 400V 50Hz
Available voltage range
3N~ 342V - 457V 50Hz
Capacity
Cooling
Rated
kW
10.0
12.5
14.0
Btu/h
34100
42700
47800
Min.-Max.
kW
4.7-11.4
5.0-14.0
5.4-16.0
Btu/h
16000-38900
17000-47800
18400-54600
Heating
Rated
kW
11.2
14.0
16.0
Btu/h
38200
47800
54600
Min.-Max.
kW
5.0-14.0
5.4-16.2
5.8-18.0
Btu/h
17100-47800
18400-55300
19800-61500
Input power
Cooling
Rated
kW
2.84
3.89
4.65
Max.
5.12
5.80
6.48
Heating
Rated
2.87
3.88
4.67
Max.
5.12
5.80
6.48
Current
Cooling
Rated
A
4.3
5.8
6.9
Heating
4.4
5.8
6.9
EER
Cooling
kW/kW
3.52
3.21
3.01
COP
Heating
3.90
3.61
3.43
Moisture removal
l/h (pints/h)
3.0 (5.3)
4.5 (7.9)
5.0 (8.8)
Maximum operating current *1
Cooling
A
7.9
8.9
9.9
Heating
7.9
8.9
9.9
Fan
Air flow
rate
Cooling
High
m
3
/h
1900
2100
2300
Med
1500
1700
1950
Low
1200
1400
1600
Quiet
1000
1100
1300
Heating
High
1900
2100
2300
Med
1500
1700
1950
Low
1200
1400
1600
Quiet
1000
1100
1300
Type × Q'ty
Sirocco× 4
Motor output
W
130
Sound pressure level
Cooling
High
dB (A)
47
49
51
Med
43
45
48
Low
37
39
42
Quiet
32
34
38
Heating
High
47
49
51
Med
43
45
48
Low
37
39
42
Quiet
32
34
38
Heat exchanger type
Dimensions (H × W × D)
mm
252 x 1350 x 39.9
252 x 1350 x 39.9
168 x 1350 x 13.3
Fin pitch
1.45
1.45
Rows x Stages
3 x 12
3 x 12 + 1 x 8
Pipe type
Copper
Fin type
Aluminium
Enclosure
Material
ABS
Colour
WHITE
(Approximate colour of MUNSELL N9.25/)
Dimensions
(H × W × D)
Net
mm
240 × 1660 × 700
Gross
318 × 1800 × 795
Weight
Net
kg
46
48
Gross
58
60
Connection pipe
Size
Liquid
mm
Ø9.52 (3/8 in.)
Gas
Ø15.88 (5/8 in.)
Method
Flare
Drain
port
Material
ABS
Size
mm
Ø21.5 (I.D.), Ø26.0 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller type
Wireless
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
The protective function might work when using it outside the operation range.
Drain hose should be field supplied.
*1 : The maximum current is the maximum value when the operated with in the operation range.