![Fujitsu AB*G18LVTB Series Design & Technical Manual Download Page 284](http://html.mh-extra.com/html/fujitsu/ab-g18lvtb-series/ab-g18lvtb-series_design-and-technical-manual_118007284.webp)
- (05-55) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
COMPLETION OF FUNCTION SETTING MODE
(11) Press the “RESET” button.
RESET
After pressing the RESET button, please set the signal code again if b,c,d setting.
SETTING UP EACH INDOOR UNIT
Repeat steps (1) through to (11). Steps (1) through to (4)
and (11) only need to carried out if the signal code is
different to the factory setting of “A”.
RESET THE POWER AFTER SETTING UP FUNCTION OF ALL
INDOOR UNITS
Important
If the reset is not performed, function can not be read in normally.
●
After all the functions have been set, the circuit breaker needs to be switched off for
●
at least 2 minutes.
After the 2 minutes has passed, power can be restored.
The set fuction is stored in the PCB and will remain in memory even when the power
●
is turned off.
However setting function is effective after power reset.
Record the function set in the indoor unit on a label, etc., and affix the label to the
unit so it can be used for after-sales service operations.
Once the "RESET" button is pressed on the remote controller, the OPERATION MODE will be
¾
set in the "AUTO MODE".
Please adjust the OPERATION MODE to either "COOLING" or "HEATING" before trying to
operate the air conditioner.
Note : If SIGNAL CODE is set to anything other than "A" ,the remote control must be set
¾