COMPLETION OF FUNCTION SETTING MODE
6) When [Cancel button] is pressed twice while “Function setting” screen is displayed, it
switches to the “Submenu” screen.
Back:
Setting:
Date and time
Submenu
[
1/2
]
Monitor
Screen
Filter sign
R.C. sensor control
Room temp. display
Off
Off
Mo 10:00AM
Cancel: OK:
Function setting
Mo 10:00AM
R.C. Function Setting
address No. No.
Version Error history
00
30
01
* If no key entry is made for 60 seconds, even though none of the above buttons is pressed,
the function setting mode will automatically be cleared.
(If the function setting mode is automatically cleared while setting addresses, activate the
mode again according to the procedure in step 2) above.)
SETTING UP EACH INDOOR UNIT
Repeat the procedures in steps 1) through 6), and set up the indoor units requiring function
setting.
RESET THE POWER AFTER SETTING UP FUNCTION OF ALL
INDOOR UNITS
Important
If the reset is not performed, function can not be read in normally.
¾
After all the functions have been set, the circuit breaker needs to be switched off
¾
for at least 2 minutes.
After the 2 minutes has passed, power can be restored.
The set function is stored in the PCB and will remain in memory even when the
¾
power is turned off.
However setting function is effective after power reset.
Record the function set in the indoor unit on a label, etc., and affix the label to the
unit so it can be used for after-sales service operations.