- (05-69) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
3) Ceiling height
Select the setting values in the table below according to the height of the ceiling.
(
... Factory setting)
Setting description
Function number
Setting value
Standard
20
00
High ceiling
01
Low ceiling (Cassette type only)
02
4) Static pressure
Select appropriate static pressure according to the installation conditions.
4-1) Duct type
(
... Factory setting)
Setting description
Function number
Setting value
Normal
21
00
High static pressure 1
01
High static pressure 2
02
High static pressure 3
03
Determine the air flow in each mode i.e., applicable range of static pressure.
CAUTION
• If the applicable static pressure does not match the static pressure mode, the static
pressure mode maybe changed to another mode automatically.
RECOMMENDED RANGE OF EXTERNAL STATIC PRESSURE [Pa]
30 to 150
4-2) Slim duct type
(
... Factory setting)
Setting description
Function number
Setting value
0 Pa
26
00
10 Pa
01
20 Pa
02
30 Pa
03
40 Pa
04
50 Pa
05
60 Pa
06
70 Pa
07
80 Pa
08
90 Pa
09
25 Pa [Standard]
31
5) Outlet directions
Select the setting values in the table below for using a 3-way outlet.
(
... Factory setting)
Setting description
Function number
Setting value
4-way
22
00
3-way
01