PEAK CUT MODE
Operation that suppressed the current value can be performed by means of the following on-
•
site work. The air conditioner is set to the Peak cut mode by applying the contact input of a
commercial ON/OFF switch to a connector on the outdoor control PC board.
Circuit diagram example
z
Use the following parts and construct a circuit like that shown above.
•
Input signal∙∙∙ON: Peak cut mode/OFF: Normal operation
•
*Set the "Peak cut mode" type by "Push switch" on the outdoor control PC board.
ON
OFF
ON
OFF
Input signal
Peak cut mode
Parts (Optional)
z
Parts name
Model name
External connect kit
UTY-XWZXZ2
Wire (External input) : Red / White / Black
Outdoor unit
control PC board
Connected unit
Connector
1
2
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10 m.
Surely insulate with
insulation tape etc. since
this wire is not used.
*10 m
Red
White
Black
Vcc
R
SW
Vcc
Power
supply
1) Power supply
●Voltage (Chart sign=Vcc) : DC 5V to 24V
●The current capacity : About 100mA
2) Switch (Chart sign=SW)
● Toggle switch or Rocker switch, etc : Switch which maintains the
states.
● Prepare switches which are enough capable for DC 10mA
current or more
3) Resistance (Chart sign=R)
●Adjust the resistance for current to about DC 10mA
(Example)
●In case of Vcc=DC 5V : Rated resistance value 470Ω 1/4W
●In case of Vcc=DC 12V : Rated resistance value 1kΩ 1/4W
●In case of Vcc=DC 24V : Rated resistance value 2.2kΩ 1/4W