- (05-32) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
SYSTEM SETTING
4.
INDOOR UNIT SETTING
4-1.
Indoor unit
Setting
Single
Simultaneous
Multi
Setting range
Setting method
Set A
Indoor unit
Primary / Secondary
-
○
"00" or "01"
Refer to 6-6.
(Function number: 51)
Set B Refrigerant circuit
address
r
r
"00" to "15"
Refer to 6-6.
(Function number: 02)
Set C Remote controller
address
r
○
"00" to "15" *1
Refer to 6-2.
(DIP SW setting)
○
: Setting is required.
r
: By a case, setting is required.
- : Setting is not required.
*1 : Set the remote controller address in the order of 00, 01, 02,…, 15.(Blank is not allowed)
SINGLE TYPE
Connection example 1
z
Connection example 2
z
Refrigerant pipe
Connection cable
Remote controller cable
SetASetBSetC
(00)(00)(00)
<Single>
Indoor unit
Outdoor unit
Wired remote controller
Connection cable
Remote controller cable
Refrigerant pipe
SetASetBSetC
(00)(00)(00)
SetASetBSetC
(00)(00)
01
<Single>
<Single>
Indoor unit
Outdoor unit
Wired remote controller
TWIN TYPE
Connection example 3
z
Connection example 4
z
Refrigerant pipe
Connection cable
Remote controller cable
SetASetBSetC
(00)(00)(00)
SetASetBSetC
01
01
(00)
<Twin>
Indoor unit
Outdoor unit
Wired remote controller
Junction box
Refrigerant pipe
Connection cable
Remote controller cable
SetASetBSetC
(00)
01 02
SetASetBSetC
01 01 03
SetASetBSetC
(00)(00)(00)
SetASetBSetC
01
01
(00)
<Twin>
<Twin>
Indoor unit
Outdoor unit
Wired remote controller
Junction box
Note : (00) is factory setting.