HIGH STATIC PRESSURE DUCT TYPE
3-3.
Type
DUCTED MODEL
INVERTER HEATPUMP
Model name
AR
Û
G45LHTA
AR
Û
G54LHTA
Power source
3N~ 400V 50Hz
Available voltage range
3N~ 342V - 457V 50Hz
Capacity
Cooling
Rated
kW
12.5
14.0
Btu/h
42700
47800
Min.-Max.
kW
5.0 - 14.0
5.4 - 16.0
Btu/h
17100 - 47800
18400 - 54600
Heating
Rated
kW
14.0
16.0
Btu/h
47800
54600
Min.-Max.
kW
5.4 - 16.2
5.8 - 18.0
Btu/h
18400 - 55300
19800 - 61500
Input power
Cooling
Rated
kW
4.06
4.65
Max.
6.14
6.83
Heating
Rated
3.67
4.37
Max.
6.14
6.83
Current
Cooling
Rated
A
6.1
6.9
Heating
5.5
6.5
EER
Cooling
kW/kW
3.08
3.01
COP
Heating
3.81
3.66
Moisture removal
l/h (pints/h)
1.5 (2.6)
2.5 (4.4)
Maximum operating current *1
Cooling
A
11.0
12.0
Heating
11.0
12.0
Fan
Airflow
rate
Cooling
High
m
3
/h
3350
3350
Med
2850
2850
Low
2430
2430
Quiet
-
-
Heating
High
3350
3350
Med
2850
2850
Low
2430
2430
Quiet
-
-
Type × Q'ty
Sirocco × 2
Motor output
W
490
Recommended static pressure
Pa
100 to 250
100 to 250
Sound pressure level
Cooling
High
dB(A)
47
47
Med
43
43
Low
40
40
Quiet
-
-
Heating
High
47
47
Med
43
43
Low
40
40
Quiet
-
-
Heat exchanger type
Dimensions (H × W × D)
mm
336 × 890 × 53.2
Fin pitch
1.30
Rows x Stages
4 × 16
Pipe type
Copper
Fin type
Aluminium
Enclosure
Material
Steel
Colour
-
Dimensions
(H × W × D)
Net
mm
400 × 1050 × 500
Gross
460 × 1230 × 640
Weight
Net
kg
46
Gross
51
Connection pipe
Size
Liquid
mm
Ø9.52 (Ø3 / 8 in.)
Gas
Ø15.88 (Ø5 / 8 in.)
Method
Flare
Drain
port
Material
Steel
Size
mm
Ø23.4 (I.D.), Ø25.4 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller type
Wired
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 100 Pa.
Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
The protective function might work when using it outside the operation range.
Drain hose should be field supplied.
*1 : The maximum current is the maximum value when the operated with in the operation range.