- (05-71) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
10) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller
temperature sensor.
(
... Factory setting)
Setting description
Function number
Setting value
No
42
00
Yes
01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller
unit sensor.
11) Cool air prevention
This setting is used to set the fan speed when the compressor stops once the room
temperature has reached the set temperature during heating operation.
(
... Factory setting)
Setting description
Function number
Setting value
Super low
43
00
Follow the setting on the remote
controller (corresponding to
ventilation)
01
12) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(
... Factory setting)
Setting description
Function number
Setting value
A
44
00
B
01
C
02
D
03
13) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
... Factory setting)
Setting description
Function number
Setting value
Operation/Stop mode
46
00
(Setting forbidden)
01
Forced stop mode
02
14) Room Temperature Control Switching
This setting is used to set the room temperature control method when the wired remote
controller is selected by the Indoor Room Temperature Sensor Switching Function.
(The unit is factory-set to “00”.)
(
... Factory setting)
Setting description
Function number
Setting value
Control by the sensors of
both the indoor unit and the
wired remote controller.
48
00
Control only by the sensor of
the wired remote controller
01