background image

6-11

6-3  Detailed Description of Parameters (Registers)

.

o

N

)

r

e

t

s

i

g

e

r

(

r

e

t

e

m

a

r

a

P

e

m

a

n

)

r

e

t

s

i

g

e

r

(

r

e

t

e

m

a

r

a

P

e

u

l

a

v

l

a

i

t

i

n

I

e

t

i

r

w

/

d

a

e

R

6

2

r

e

t

s

i

g

e

r

n

o

i

t

a

r

e

l

e

c

e

d

/

n

o

i

t

a

r

e

l

e

c

c

A

8

2

1

)

e

t

o

N

(

e

t

i

r

W

<Description>

• Deceleration time control register (the acceleration for quick stop is set)
• Writing is possible at the desired timing.
• The setting of the acceleration/deceleration register 2 is enabled only in the pulse generation mode.

.

o

N

)

r

e

t

s

i

g

e

r

(

r

e

t

e

m

a

r

a

P

e

m

a

n

)

r

e

t

s

i

g

e

r

(

r

e

t

e

m

a

r

a

P

e

u

l

a

v

l

a

i

t

i

n

I

e

t

i

r

w

/

d

a

e

R

7

r

e

t

s

i

g

e

r

n

o

i

t

a

c

il

p

i

t

l

u

m

d

e

e

p

S

3

6

)

e

t

o

N

(

e

t

i

r

W

<Description>

• This is the maximum command frequency control register.
• When the reference clock of this module (NP1F-MP1/NP1F-MP2) is 25MHz, the maximum command frequency is

calculated from the following formula:

Maximum command frequency = 25000kHz / (Set value of speed multiplication re 1) x (1/2)

• The resolution of the command pulse frequency is 16-bit/20-bit width with respect to maximum command

frequency.

Precaution:

·  The write command, from the CPU module into the speed multiplication register, is enabled only in the pulse 
    generation mode. 
·  In position command mode, data from the CPU module is invalid.

(Data is automatically set by the positioning module.)

.

o

N

)

r

e

t

s

i

g

e

r

(

r

e

t

e

m

a

r

a

P

e

m

a

n

)

r

e

t

s

i

g

e

r

(

r

e

t

e

m

a

r

a

P

e

u

l

a

v

l

a

i

t

i

n

I

e

t

i

r

w

/

d

a

e

R

8

r

e

t

n

u

o

c

e

s

l

u

p

d

n

a

m

m

o

C

0

d

a

e

R

<Description>

• 16-bit (65535) ring counter which counts up or down according to the command pulse.
• Command pulse counter is for read only.
• In this area, counting up or down is performed according to the direction of the command pulse.

Forward command pulse: Count up
Reverse command pulse: Count down

• When overflowed, the counter value changes as follows:

When counting up:

1111 1111 1111 1111 ==>  0000 0000 0000 0000

When counting down: 0000 0000 0000 0000 ==>  1111 1111 1111 1111

• This counter is cleared to zero when reset by powering on or at the rising edge of the current value counter reset

command.

• The command pulse counter is enabled in the pulse generation mode and position command mode.

Summary of Contents for micrex-sx NP1F-MP1

Page 1: ...FEH214a series USER S MANUAL PULSE TRAIN POSITIONING CONTROL COMBINED MODULE...

Page 2: ...a e c n e r e f e R n i w 0 0 3 D l a u n a M s r e s U s e i r e s X S X E R C I M 4 5 2 H E F e h t f o l l a d n a n i w 0 0 3 D f o n o c i d n a u n e m e h t s n i a l p x E n i w 0 0 3 D f o s...

Page 3: ...while the power is turned ON It may result in an electric shock to theoperator Turn OFF the power before mounting dismounting wiring maintaining or checking otherwise electric shock erratic operation...

Page 4: ...ong operation might break or cause machine problems Engage the loader connector in a correct orientation otherwise an erratic operation might occur Before touching the PC discharge any static electric...

Page 5: ...c e h t n o n w o h s s i o N l a u n a M n o d e t n i r P o N l a u n a M s t n e t n o c n o i s i v e R 8 9 9 1 p e S 4 1 2 H E F n o i t i d e t s r i F 2 0 0 2 n a J a 4 1 2 H E F d e n i f e R...

Page 6: ...axes 3 6 3 3 3 NP2F LEV Signal converter 3 8 3 4 Dimensions 3 10 3 4 1 NP1F MP1 for 1 axis 3 10 3 4 2 NP1F MP2 for 2 axes 3 10 3 4 3 NP2F LEV Signal converter 3 11 Section 4 Wiring 4 1 4 1 Mounting P...

Page 7: ...de 7 4 7 3 1 Positional deviation calculation function 7 5 7 3 2 Command pulse count control 7 6 7 3 3 Command pulse frequency control 7 7 7 3 4 Trapezoidal acceleration deceleration 7 8 7 3 5 Automat...

Page 8: ...ission error has been detected 7 36 7 4 10 Operation for resetting deviation 7 37 7 4 11 Backlash compensation 7 37 7 4 12 Feedback pulse multiplication 7 37 7 5 External Input Pulse Functions 7 39 7...

Page 9: ...s 1 1 1 Handling precautions as precision device 1 1 2 Precautions concerning operating conditions and environment 1 1 1 2 Functional Overview 1 2 1 2 1 Overview of NP1F MP1 NP1F MP2 functions 1 2 1 2...

Page 10: ...where the temperature is too high or low or the humidity is too high Operating ambient temperature 0 to 55 C Operating ambient humidity 20 to 95 RH 7 In places with extremely low humidity excessive st...

Page 11: ...i t a l u c l a c c i t a m o t u A F I l a i r e s F I e d i s U P C s d r o w 4 1 l a t o t s d r o w 4 t u p t u o s d r o w 0 1 t u p n i 1 P M F 1 P N s d r o w 2 2 l a t o t s d r o w 8 t u p t...

Page 12: ...e v i r d e n i l l a n g i s l a i t n e r e f f i D y c n e u q e r f t u p t u O z H M 1 x a M A sample connection configuration of the NP2F LEV is shown below Sample connection configuration of t...

Page 13: ...on configuration of the NP2F LEV NP1F MP1 NP2F LEV NP2F LEV Serial I F External I Fs X axis forward pulse X axis reverse pulse External pulse DI X axis EMG OT origin LS interrupt DO Command output fro...

Page 14: ...nfiguration of Peripheral Equipment 2 1 2 2 Applied System 2 2 2 2 1 Applicable CPU 2 2 2 2 2 Applied system configuration 2 2 1 For a 2 axis system 2 2 2 Sample extensions for 8 axis system 2 2 2 3 L...

Page 15: ...D300win Positioning loader software Various type expansion FBs for positioning General purpose PC SX bus Precaution This module only contains the basic functions for positioning processing Motion rel...

Page 16: ...rol module NP1F MP2 Input module NP1X1606 W Output module NP1Y16T09P6 2 axes CPU module Positioning control module Input module Output module Power supply module 2 Sample extensions for 8 axis system...

Page 17: ...p A B F k c o l b n o i t c n u f n o i s n a p x E l o r t n o c g n i n o i t i s o p r o f e g a k c a p F P T P N 4 P N s i x a t n e d n e p e d n i r o f s m a r g o r p n o i t a c i l p p A l...

Page 18: ...LEV 3 2 3 2 Specifications NP1F MP1 NP1F MP2 3 3 3 2 1 Specifications NP2F LEV 3 3 3 3 Names 3 4 3 3 1 NP1F MP1 for 1 axis 3 4 3 3 2 NP1F MP2 for 2 axes 3 6 3 3 3 NP2F LEV Signal converter 3 8 3 4 Di...

Page 19: ...r o m r o a P k 0 7 l a c i n a h c e M e c i v r e s s n o i t i d n o c n o i t a r b i V s m 6 9 1 n o i t a r e l e c c a t n a t s n o C m m 5 1 0 e d u t i l p m a f l a H 2 s r u o h x i s l a...

Page 20: ...0 0 3 o t t n e l a v i u q e e r o m r o a P k 0 7 l a c i n a h c e M e c i v r e s s n o i t i d n o c n o i t a r b i V s m 6 9 1 n o i t a r e l e c c a t n a t s n o C m m 5 1 0 e d u t i l p m...

Page 21: ...5 e p y t t u p n I l a n g i s l a i t n e r e f f i d r o t u p n i r o t c e l l o c n e p O 0 9 e s l u p e s r e v e r e s l u p d r a w r o f r o Z e s a h p d n a B e s a h p A e s a h p e c n...

Page 22: ...r u T n e e r G Y D R y d a e R l a m r o n s i e l u d o m e h t n e h w n o s n r u T d e R M L A r o r r E e r a w d r a h e h t n i r o m a r g o r p n o i t a c i l p p a e h t n i s r u c c o r...

Page 23: ...R t u p t u o 9 A e s l u p d r a w r o F t u p t u o 8 B M O C t u p t u o e s l u P 8 A M O C t u p t u o e s l u P 7 B e s l u p k c a b d e e F B e s a h p 7 A e s l u p k c a b d e e F A e s a h...

Page 24: ...n a n e h w n o s n r u T n e e r G Y D R y d a e R l a m r o n s i e l u d o m e h t n e h w n o s n r u T d e R M L A r o r r E e r a w d r a h e h t n i r o m a r g o r p n o i t a c i l p p a e h...

Page 25: ...a h p 6 A e s l u p k c a b d e e F A e s a h p 5 B e s l u p k c a b d e e F D N G 5 A e s l u p k c a b d e e F D N G 4 B t i n u e s l u p l a u n a M D N G 4 A e s l u p k c a b d e e F Z e s a h...

Page 26: ...u T 2 Connector pin layout for the external I O signal A front view the upper side A front view the lower side Connector pin layout 9 pin Connector pin layout 16 pin 1 2 3 4 5 6 7 8 9 A 1 2 3 4 5 6 7...

Page 27: ...a i t n e r e f f i d V 5 9 1 B N 1 O N t u p t u o l a i t n e r e f f i d V 5 2 2 A P 2 O N t u p t u o l a i t n e r e f f i d V 5 0 1 2 B N 2 O N t u p t u o l a i t n e r e f f i d V 5 3 3 A P 3...

Page 28: ...3 10 3 4 Dimensions 3 4 1 NP1F MP1 for 1 axis 3 4 2 NP1F MP2 for 2 axes 90 46 5 75 35 105...

Page 29: ...3 11 3 4 Dimensions 3 4 3 NP2F LEV Signal converter 95 47 2 10 29 8 39 8 85 95 40 36 6...

Page 30: ...4 3 1 External I O signal specifications NP1F MP2 4 10 4 3 2 External I O signal interface NP1F MP2 4 11 4 4 Connector Pin Layout for the External Connection Signal Converter 4 17 4 4 1 External I O s...

Page 31: ...a 2 2 A M F 1 P N A 5 1 0 l o r t n o c g n i n o i t i s o p s e x a 2 2 P H F 1 P N A 5 9 0 0 r e t n u o c d e e p s h g i H 2 C H F 1 P N A 5 8 0 0 e s o p r u p l a r e n e G n o i t a c i n u m...

Page 32: ...rately If I O wiring cannot be separated from the power cables or the main circuit cables bound shield cables must be used and the shield must be grounded at the PC end To wire the pulse output shield...

Page 33: ...8 A M O C t u p t u o e s l u P 7 B e s l u p k c a b d e e F B e s a h p 7 A e s l u p k c a b d e e F A e s a h p 6 B e s l u p k c a b d e e F B e s a h p 6 A e s l u p k c a b d e e F A e s a h p...

Page 34: ...k c a b d e e f f o t u p n I D N G e s l u p k c a b d e e F 5 B 1 H C l a n g i s V 0 e s l u p k c a b d e e f f o t u p n I t u p n I l a n g i s t u p n i l a n r e t x E t u p n i t p u r r e t...

Page 35: ...mand signal 120 Phase A Phase B Phase A Phase B 120 1 2k A2 A1 120 120 1 2k 220 220 B2 B1 B3 B4 5V 0V Manual pulse unit side CH1 side When the manual pulse unit utilizes open collectors Phase A Phase...

Page 36: ...B Phase Z Phase A Phase B Phase Z 120 120 1 2k A7 A6 B7 B6 A4 A3 Servo side When the feedback pulse signal is driven by a open collector A5 B5 120 120 1 2k 120 120 1 2k 220 220 220 CH1 side 120 120 1...

Page 37: ...name Circuit External input signal Pulse output signal 24V A14 B16 B17 A17 A15 A16 OT OT Emergency stop Interrupt Origin LS 3 9k 3 9k 3 9k 3 9k 3 9k 820 CH1 side 820 820 820 820 CH1 side A9 A8 B9 B8...

Page 38: ...4 8 4 2 Connector Pin Layout for the External Connection NP1F MP1 Signal name Circuit External output signal A13 A12 24V Ry B12 Ry B11 CH1 side 3 9k 3 9k A11 B13...

Page 39: ...B e s l u p l a u n a M D N G t i n u 4 A e s l u p k c a b d e e F Z e s a h p 3 B e s l u p l a u n a M D N G t i n u 3 A e s l u p k c a b d e e F Z e s a h p 2 B e s l u p l a u n a M B e s a h p...

Page 40: ...s l a i t n e r e f f i d 0 1 1 e c n a d e p m i t u p n I s s e l r o y c n e u q e r f e s l u p t u p n I s p p k 0 0 5 x a M e r o m r o V 5 3 e g n a r e g a t l o v N O V 5 1 o t 0 e g n a r e...

Page 41: ...mmand signal 120 Phase A Phase B Phase A Phase B 120 1 2k A2 A1 120 120 1 2k 220 220 B2 B1 B3 B4 5V 0V Manual pulse unit side CH1 side When the manual pulse unit utilizes open collectors When the manu...

Page 42: ...Z Phase A Phase B Phase Z 120 120 1 2k A7 A6 B7 B6 A4 A3 Servo side When the feedback pulse signal is driven by a open collector A5 B5 120 120 1 2k 120 120 1 2k 220 220 220 CH1 side 5V Phase A Phase B...

Page 43: ...hase Z Phase A Phase B Phase Z 120 120 1 2k When the feedback pulse signal is driven by a line driver 120 120 1 2k 120 120 1 2k 220 220 220 CH2 side Servo side A7 A6 B7 B6 A4 A3 A5 B5 Phase A Phase B...

Page 44: ...signal 24V CH1 A14 CH1 B16 CH1 B17 CH1 A17 CH1 A15 CH1 A16 OT OT Emergency stop Interrupt Origin LS 3 9k 3 9k 3 9k 3 9k 3 9k 820 CH1 side 820 820 820 820 CH2 side 24V CH2 A14 CH2 B16 CH2 B17 CH2 A17...

Page 45: ...ayout for the External Connection NP1F MP2 Signal name Circuit Pulse output signal CH2 side Servo side CH1 side A9 A8 B9 B8 CA CA CB CB CM Servo side When the servo device utilizes open collectors A9...

Page 46: ...Connector Pin Layout for the External Connection NP1F MP2 Signal name Circuit External output signal A13 A12 24V Ry B12 Ry A11 CH1 side 3 9k 3 9k A13 A12 24V Ry B12 Ry A11 CH2 side 3 9k 3 9k B11 B13...

Page 47: ...6 pin o N n i P e m a n l a n g i S o N n i P e m a n l a n g i S 1 1 A P 1 T U O t u p t u o l a i t n e r e f f i d V 5 9 1 B N 1 T U O t u p t u o l a i t n e r e f f i d V 5 2 2 A P 2 T U O t u p...

Page 48: ...n I e r o m r o V 5 3 e g n a r e g a t l o v N O V 5 1 o t 0 e g n a r e g a t l o v F F O e m i t y a l e d t u p n I 1 N O o t F F O s s e l r o s 1 F F O o t N O s s e l r o s r o t c e n n o c e...

Page 49: ...ection Signal Converter 4 4 2 External I O signal interface Signal converter Signal name Circuit Input side connector 9 pin 220 390 10k 5V 220 390 10k 5V 220 390 10k 5V 220 390 10k 5V 6 7 8 9 1 2 3 4...

Page 50: ...4 20 4 4 Connector Pin Layout for the External Connection Signal Converter Signal name Circuit Output side connector 16 pin A1 B1 A2 B2 A3 B3 A4 B4 A8 A7 B8 B7 A5 B5 Connector side 24V Servo side 0V...

Page 51: ...terclockwise Forward rotation CW Clockwise Reverse rotation The direction indication of the motor rotation is the shaft view from the motor mounted side 1 When the NP1F MP1 or the NP1F MP2 generates t...

Page 52: ...S EMG OT input B16 OT input 9 34 10 35 33 36 38 40 39 41 CA CA CB CB M5 FA FB FZ M5 M5 7 6 30 29 32 31 VIN2 M5 VIN3 M5 VIN4 M5 25 24 18 17 P24 P24 M24 M24 50 CONT1 3 5 4 P10 VIN1 M5 28 N10 RUN 49 CONT...

Page 53: ...pulse phase Z Feedback pulse phase Z Feedback pulse GND Feedback pulse GND A11 A13 A14 Output COM For output 24V DC Input COM1 A19 A20 0V DC 24V DC Input COM A15 A16 A17 B17 Input COM1 Origin LS EMG O...

Page 54: ...Wiring of a connector type module Usable connector and applicable cable size are shown below n o i t a c i f i s s a l C u s t i j u F e p y T e z i s e l b a C e p y t d e r e d l o S t e k c o S U...

Page 55: ...atus signal address No 0 lower word 5 36 2 Ch1 bit data signal Status signal address No 1 upper word 5 46 3 Ch1 current value read Address No 2 lower word address No 3 upper word 5 50 4 Current comman...

Page 56: ...M F 1 P N o N s s e r d d A e m a N 0 r e t s i g e r y c n e u q e r f t e g r a T 1 r e t s i g e r y c n e u q e r f e s a B 2 r e t s i g e r y c n e u q e r f t n e r r u C 3 r e t s i g e r e s...

Page 57: ...read 9 Current external pulse data read 10 Bit command signal 11 Bit command signal 12 Set value area 13 Set value area External pulse input counter Module detection time lower word PC MP1 lower word...

Page 58: ...c e x e 6 n o i t c e t e d l a n g i s Z e s a h P d e t c e t e d s i Z e s a h p n e h w N O d e l b a n e s i n o i t c e t e d l a n g i s Z e s a h p e l i h W 7 n o i t c e t e d n o i t i s o...

Page 59: ...atus of the command pulse register becomes 1 one when pulse output is completed or when command pulse register reset signal is issued Select register PC MP1 Set value data PC MP1 Write command PC MP1...

Page 60: ...d signal is 0 because the command pulse is being output Positioning end signal is 1 because the positioning end signal has been detected Outputting command pulse internal signal Near zero PC MP1 Posit...

Page 61: ...utput is stopped Sign command PC MP1 Start command PC MP1 Rotation direction PC MP1 Positioning end PC MP1 1 0 1 1 1 1 1 0 Outputting reverse pulse Outputting forward pulse In the position command mod...

Page 62: ...is is a response signal to the speed change command in the pulse generation mode While this signal is 1 the values stored in the set value data area are continuously written in the target frequency re...

Page 63: ...t i B Description The external pulse interrupt position detect signal becomes 1 when external pulse interrupt signal is detected after the external pulse interrupt position detect command has become...

Page 64: ...set PC MP1 1 Error signal cannot be reset because the emergency stop signal input is OFF 1 1 r o r r e T O e m a n l a n g i S 1 1 t i B Description When the OT signal is enabled in the pulse generati...

Page 65: ...ON OFF 1 Error signal cannot be reset because the command pulse register reset signal is OFF 1 Alarm reset PC MP1 1 Error signal cannot be reset because OT input is OFF 1 1 d e s u t o N e m a n l a...

Page 66: ...ecomes 1 When the rising edge at which the command pulse register reset signal changes from 0 to 1 and the rising edge at which alarm reset signal changes from 0 to 1 are detected this signal returns...

Page 67: ...a z i l a i t i n i n e h w 1 7 e t i r w a t a d o t e s n o p s e R d n a m m o c e t i r w a t a d o t l a n g i s e s n o p s e R 8 y a l p s i d d n a m m o c r e t s i g e r d a e R s i r e t s...

Page 68: ...lectable Inputs DI1 to DI3 become 1 when external contact is released Inputs DI4 and DI5 and the phase Z input signal become as follows when input level is selected by the control register For NO cont...

Page 69: ...0 0 0 1 Near zero monitoring register 1 1 0 1 1 Pulse count setting 16 1 1 1 0 0 1 1 1 0 1 1 1 1 1 0 1 1 1 1 1 1 1 0 1 0 Pulse count setting upper 1 1 0 0 1 Pulse count setting middle 1 1 0 0 0 Pulse...

Page 70: ...en written in 4th stage 1 Precautions Data is normally written in the target frequency FIFO buffer because registration in the FIFO buffer is not executed by the target frequency FIFO buffer write com...

Page 71: ...o l r e t n u o c e t o N d e t c e t e d s a w d r o w r e w o l r e t n u o c e u l a v t n e r r u C e v o b a n a h t r e h t O d r o w r e p p u r e t n u o c e u l a v t n e r r u C d r o w r e...

Page 72: ...tn 1 Tn x 1000 x 1000 Precautions The time until module detection time overflows is 65 5ms When an overflow has occurred this value returns to 0 and the timer count is continued ring operation Feedbac...

Page 73: ...o i t i s o P e d o m g n i n o i t i s o p t p u r r e t n i N O n e h W t n i o p n o i t c e t e d l a n g i s t p u r r e t n i r o Z e s a h p 9 t p u r r e t n i e s l u p l a n r e t x E d n a...

Page 74: ...signal to see whether the positioning operation has ended or not With the start command set to 0 when stopped after decelerating when emergency stopped or when an error has been detected monitor unti...

Page 75: ...viation amount when phase Z or interrupt signal was detected 1 The lower word of current value counter when phase Z or interrupt signal was detected t e s e r r e t n u o c e u l a v t n e r r u C e m...

Page 76: ...ted without stopping the operation for changing speed from the PC The writing in the target frequency register uses 2 words of the set value data area and therefore is set to stop the speed change pro...

Page 77: ...1 0 1 2 Current value Deviation amount Upper word of current data Data is held Upper word of current value Latch data select PC MP1 3 4 1 Not detected because phase Z detect command is 0 2 Not accepte...

Page 78: ...rupt signal input external input Current value data PC MP1 1 1 0 1 2 Current value Deviation amount Upper word of current value data Upper word of current value data Data is held Latch data select PC...

Page 79: ...by setting the control register Command pulse is output while detect command signals are both 0 Example of phase Z signal position detection Interrupt mode PC MP1 Start command PC MP1 Positioning end...

Page 80: ...input Interrupt detection PC MP1 1 1 1 1 1 1 The deviation amount and current feedback value when interrupt was detected are latched Not accepted because interrupt detect command is 0 In the position...

Page 81: ...PC MP1 Command pulse zero PC MP1 1 1 1 1 0 In the position command mode the start signal for module internal processing is cleared to zero and pulse output is immediately stopped Precautions When auto...

Page 82: ...on Acceleration deceleration register 2 In the position command mode the start signal for module internal processing is cleared to zero and pulse output is immediately stopped To emergency stop from t...

Page 83: ...over error t e s e r t n u o m a n o i t a i v e D e m a n l a n g i S 4 1 t i B Description While this signal is 1 the deviation amount is forcibly reset to zero For module internal processing while...

Page 84: ...neration mode position command mode Error monitoring time is set in the monitor register from the CPU module max 6553 5ms in 0 1ms steps When monitoring time is set to 0 zero transmission error monito...

Page 85: ...ed 0 1 1 0 0 0 1 1 0 1 Error monitoring timer register 0 1 1 1 0 Control register 0 1 1 1 1 Backlash register 1 0 0 0 0 Near zero monitor register 1 0 0 0 1 Deviation over monitor register High speed...

Page 86: ...nd PC MP1 Response to write command PC MP1 1 1 1 1 Writing in each register is possible at the desired timing Precautions In the pulse generation mode deceleration point detection during automatic ope...

Page 87: ...0 0 1 1 0 1 Error monitoring timer register 0 1 1 1 0 Control register 0 1 1 1 1 Backlash register 1 0 0 0 0 Near zero monitor register 1 0 0 0 1 Deviation over monitor register High speed limiter reg...

Page 88: ...ead command PC MP1 Response to read command PC MP1 Current value data PC MP1 1 1 1 1 Current value Current value Data Data Data can be read from individual registers at the desired timing While the re...

Page 89: ...as binary data Effective number of bits is determined by the bit width of each register The part exceeding the bit width of each register is ignored In the position command mode While the start comma...

Page 90: ...ternal pulse input counter 13 Module detection time 14 Ch1 Bit command signal 15 Ch1 Bit command signal 16 Ch1 Set value 17 Ch1 Set value 18 Ch2 Bit command signal 19 Ch2 Bit command signal 20 Ch2 Set...

Page 91: ...a n g i s Z e s a h p e l i h W 7 t c e t e d n o i t i s o p t p u r r e t n I s i l a n g i s t p u r r e t n i e h t n e h w N O d e l b a n e s i n o i t c e t e d l a n g i s t p u r r e t n i e...

Page 92: ...ommand PC MP2 Response to write command PC MP2 Start command PC MP2 Positioning end PC MP2 Command pulse zero PC MP2 Near zero PC MP2 1 10 000 00011 1 1 1 1 1 1 1 1 Pulse outputting In the position co...

Page 93: ...gnal Near zero PC MP2 Positioning end PC MP2 1 1 1 0 1 Positioning end signal is 0 because the command pulse is being output Positioning end signal is 1 because the positioning end signal has been det...

Page 94: ...pulse output is stopped Sign select PC MP2 Start command PC MP2 Rotating direction PC MP2 Positioning end PC MP2 1 0 1 1 1 1 Outputting reverse pulse Outputting forward pulse 1 0 In the position comma...

Page 95: ...r is reset 1 FIFO buffer for command pulse register is reset In the position command mode when the command pulse register reset command is issued the start signal is turned OFF and pulse output is sto...

Page 96: ...e For details refer to the paragraph for phase Z signal detect command t c e t e d n o i t i s o p t p u r r e t n I e m a n l a n g i S 7 t i B Description In the pulse generation mode or position co...

Page 97: ...generation mode this signal becomes 1 while the accelerating decelerating operation is being executed by this module while the frequency of the command pulse is changing Frequency Time Start command...

Page 98: ...annot be reset because the emergency stop signal input is OFF 1 1 r o r r e T O e m a n l a n g i S 1 1 t i B Description When the OT signal is enabled in the pulse generation mode or position command...

Page 99: ...FF 1 Error signal cannot be reset because the command pulse register reset is OFF 1 Alarm reset PC MP2 1 Error signal cannot be reset because OT input is OFF 1 1 d e s u t o N e m a n l a n g i S 3 1...

Page 100: ...becomes 1 When the rising edge at which the command pulse register reset signal changes from 0 to 1 and the rising edge at which alarm reset signal changes from 0 to 1 are detected this signal return...

Page 101: ...t a z i l a i t i n i n e h w 1 7 e t i r w a t a d o t e s n o p s e R d n a m m o c e t i r w a t a d o t l a n g i s e s n o p s e R 8 y a l p s i d d n a m m o c r e t s i g e r d a e R s i r e t...

Page 102: ...ts become 1 when external contact is released DI4 and DI5 inputs and phase Z input signal become as follows when the input level is selected by the control register For NO contact input 1 when externa...

Page 103: ...er 1 0 0 0 1 Near zero monitoring register 1 1 0 1 1 Pulse count setting 16 1 1 1 0 0 1 1 1 0 1 1 1 1 1 0 1 1 1 1 1 1 1 0 1 0 Pulse count setting upper 1 1 0 0 1 Pulse count setting middle 1 1 0 0 0 P...

Page 104: ...r Precautions Data is normally written in the target frequency FIFO buffer because registration in the FIFO buffer is not executed by the target frequency FIFO buffer write command When writing to the...

Page 105: ...o l r e t n u o c e u l a v t n e r r u C 1 d n a m m o c t c e t e d t p u r r e t n I t n e r r u c e h t f o e u l a v e h t r o t n u o m a n o i t a i v e D t p u r r e t n i e h t n e h w d r o...

Page 106: ...i r w s u o u n i t n o c N O e l i h W 6 t c e t e d l a n g i s Z e s a h P d e t c e t e d s i Z e s a h p n e h w N O d e l b a n e s i n o i t c e t e d l a n g i s Z e s a h p e l i h W 7 t c e...

Page 107: ...mand pulse register becomes 1 when pulse output is completed when the command pulse register reset command is issued Register select PC MP2 Set value data PC MP2 Write command PC MP2 Response to write...

Page 108: ...g command pulse internal signal Near zero PC MP2 Positioning end PC MP2 1 1 1 0 1 Positioning end signal is 0 because the command pulse is being output Positioning end signal is 1 because the position...

Page 109: ...n select PC MP2 Start command PC MP2 Rotating direction PC MP2 Positioning end PC MP2 1 0 1 1 1 1 Outputting reverse pulse Outputting forward pulse 1 0 In the position command mode this signal changes...

Page 110: ...is reset 1 FIFO buffer for command pulse register is reset In the position command mode when the command pulse register reset command is issued the start signal is turned OFF and pulse output is stopp...

Page 111: ...For details refer to the paragraph for phase Z signal detect command t c e t e d n o i t i s o p t p u r r e t n I e m a n l a n g i S 7 t i B Description In the pulse generation mode or position comm...

Page 112: ...se generation mode this signal becomes 1 while the accelerating decelerating operation is being executed by this module while the frequency of command pulse is changing Frequency Time Start command PC...

Page 113: ...annot be reset because the emergency stop signal input is OFF 1 1 r o r r e T O e m a n l a n g i S 1 1 t i B Description When the OT signal is enabled in the pulse generation mode or position command...

Page 114: ...d the rising edge at which alarm reset signal changes from 0 to 1 are detected this signal returns to 0 When an OT error is detected no command in the reverse direction will be accepted Enabling disab...

Page 115: ...cted When a deviation over error is detected the positioning control module falls into non fatal error condition RAS code 0D6hex r o r r e n o i s s i m s n a r T e m a n l a n g i S 5 1 t i B Descrip...

Page 116: ...e r e s l u p d n a m m o C l a n g i s m r a l a w o l f r e v o r e t s i g e r e s l u p d n a m m o C 4 1 l l u f r e f f u b O F I F l l u f s i r e f f u b O F I F e g a t s 4 n e h w 1 5 1 d a...

Page 117: ...this the signal continues to be 1 Precaution This signal becomes 0 while a deviation over error is detected e t i r w a t a d o t e s n o p s e R e m a n l a n g i S 7 t i B Description This is a resp...

Page 118: ...register 1 0 0 0 0 Backlash register 1 0 0 0 1 Near zero monitoring register 1 1 0 1 1 Pulse count setting 16 1 1 1 0 0 1 1 1 0 1 1 1 1 1 0 1 1 1 1 1 1 1 0 1 0 Pulse count setting upper 1 1 0 0 1 Puls...

Page 119: ...No of command pulse register Precautions Data is normally written in the target frequency FIFO buffer Because registration in the FIFO buffer is not executed by the target frequency FIFO buffer write...

Page 120: ...e t e d s a w l a n g i s d r o w r e w o l r e t n u o c e u l a v t n e r r u C e v o b a n a h t r e h t O d r o w r e p p u r e t n u o c e u l a v t n e r r u C d r o w r e w o l r e t n u o c e...

Page 121: ...he external pulse input frequency can be calculated f Frequency Hz T Takt time s tn 1 Previous module detection time s tn Current module detection time s Pn 1 Previous count value pulse Pn Current cou...

Page 122: ...r r e t n i r e t f a t u p t u o s i e s l u p f o t n u o m a 8 e d o m t p u r r e t n I h t g n e l d e i f i c e p s a t n i o p a t a s n o i t i s o P e d o m g n i n o i t i s o p t n i o p t...

Page 123: ...signal to see whether the positioning operation has ended or not When stopped after decelerating when emergency stopped or when an error has been detected with the start command set to 0 monitor unti...

Page 124: ...amount when phase Z or interrupt signal was detected 1 The lower word of the current value counter when phase Z or interrupt signal was detected t e s e r r e t n u o c e u l a v t n e r r u C e m a n...

Page 125: ...without stopping the operation for changing speed from the PC The writing in the target frequency register uses 2 words of the set value data area and therefore is set after stopping the processing fo...

Page 126: ...1 3 4 2 Current value Deviation amount Upper word of current data Data is held Upper word of current value Latch data select PC MP2 1 Not detected because the phase Z detect command is 0 2 Not accept...

Page 127: ...ignal input external input Current value data 2 PC MP2 1 1 0 1 3 4 2 Current value Deviation amount Upper word of current value Data is held Upper word of current value Latch data select PC MP2 1 Not...

Page 128: ...y setting the control register Command pulse is output while detect command signals are both 0 Example of phase Z signal position detection Start command PC MP2 Positioning end PC MP2 Command pulse ze...

Page 129: ...on amount and the current feedback value when interrupt was detected are latched Not accepted because interrupt detect command is 0 Frequency Hz Set value of command pulse register Time t In position...

Page 130: ...start signal for module internal processing is cleared to zero and pulse output is immediately stopped Precautions When automatic computation of the deceleration point is enabled the deceleration poi...

Page 131: ...tion Acceleration deceleration register 2 In position command mode the start signal for module internal processing is cleared to zero and pulse output is immediately stopped To emergency stop from the...

Page 132: ...over error t e s e r t n u o m a n o i t a i v e D e m a n l a n g i S 4 1 t i B Description While this signal is 1 the deviation amount is forcibly reset to zero For module internal processing while...

Page 133: ...x 6553 5ms in 0 1ms steps When monitoring time is set to 0 zero transmission error monitoring is not performed Even when monitoring time is set to zero after an error has been detected the error detec...

Page 134: ...used 0 1 1 0 0 0 1 1 0 1 Error monitoring timer register 0 1 1 1 0 Control register 0 1 1 1 1 Backlash register 1 0 0 0 0 Near zero monitor register 1 0 0 0 1 Deviation over monitor register High spe...

Page 135: ...ue data PC MP2 1 1 Write command PC MP2 1 1 Response to write command PC MP2 Writing in each register is possible at the desired timing Precautions In the pulse generation mode deceleration point dete...

Page 136: ...0 1 1 Not used 0 1 1 0 0 0 1 1 0 1 Error monitoring timer register 0 1 1 1 0 Control register 0 1 1 1 1 Backlash register 1 0 0 0 0 Near zero monitor register 1 0 0 0 1 Deviation over monitor registe...

Page 137: ...output When the FIFO buffer is empty the value of both the target frequency FIFO buffer and command pulse count FIFO buffer becomes 0 zero 3 Ch1 set value area Write signal address Nos 16 and 17 o N s...

Page 138: ...t f a t u p t u o s i e s l u p f o t n u o m a 8 e d o m t p u r r e t n I h t g n e l d e i f i c e p s a t n i o p a t a s n o i t i s o P e d o m g n i n o i t i s o p t n i o p t p u r r e t n i...

Page 139: ...zero signal to see whether positioning operation has ended or not When stopped after decelerating when emergency stopped or when an error has been detected with the start command set to 0 monitor unti...

Page 140: ...amount when phase Z or interrupt signal was detected 1 The lower word of the current value counter when phase Z or interrupt signal was detected t e s e r r e t n u o c e u l a v t n e r r u C e m a n...

Page 141: ...ation for changing speed from the PC The writing in the target frequency register uses 2 words of the set value data area and therefore is set after stopping the processing for speed change For detail...

Page 142: ...3 4 2 Current value Deviation amount Upper word of current data Data is held Upper word of current value Latch data select PC MP2 1 Not detected because the phase Z detect command is 0 2 Not accepted...

Page 143: ...put Current value data 2 PC MP2 1 1 0 1 3 4 2 Current value Deviation amount Upper word of current value Data is held Upper word of current value Latch data select PC MP2 1 Not detected because the in...

Page 144: ...by setting the control register Command pulse is output while both detect command signals are 0 Example of phase Z signal position detection Start command PC MP2 Positioning end PC MP2 Command pulse...

Page 145: ...deviation amount and the current feedback value when interrupt was detected are latched Not accepted because interrupt detect command is 0 Frequency Hz Set value of command pulse register Time t In po...

Page 146: ...command mode the start signal is cleared to zero and pulse output is immediately stopped Precautions When automatic computation of the deceleration point is enabled the deceleration point register is...

Page 147: ...1 Quick stop motion Acceleration deceleration register 2 In position command mode the start signal is cleared to zero and pulse output is immediately stopped To emergency stop from the CPU module side...

Page 148: ...over error t e s e r t n u o m a n o i t a i v e D e m a n l a n g i S 4 1 t i B Description While this signal is 1 the deviation amount is forcibly reset to zero For module internal processing while...

Page 149: ...ms in 0 1ms steps When the monitoring time is set to 0 zero transmission error monitoring is not performed Even when the monitoring time is set to zero after an error has been detected the error detec...

Page 150: ...used 0 1 1 0 0 0 1 1 0 1 Error monitoring timer register 0 1 1 1 0 Control register 0 1 1 1 1 Backlash register 1 0 0 0 0 Near zero monitor register 1 0 0 0 1 Deviation over monitor register High spe...

Page 151: ...command PC MP2 1 1 Response to write command PC MP2 Writing in each register is possible at the desired timing Precautions In the pulse generation mode deceleration point detection during automatic op...

Page 152: ...0 1 1 Not used 0 1 1 0 0 0 1 1 0 1 Error monitoring timer register 0 1 1 1 0 Control register 0 1 1 1 1 Backlash register 1 0 0 0 0 Near zero monitor register 1 0 0 0 1 Deviation over monitor registe...

Page 153: ...pty the value of both the target frequency FIFO buffer and command pulse count FIFO buffer becomes 0 zero 6 Set value area Write signal address Nos 20 and 21 o N s s e r d d A 5 1 4 1 3 1 2 1 1 1 0 1...

Page 154: ...en reading by above method 2 Set the register number from which data is to be read in the read register NP1F MP1 Address No 11 bit 8 to bit C refer to page 5 32 NP1F MP2 Address No 15 bit 8 to bit C r...

Page 155: ...ter 1 0 0 0 1 Deviation over monitor register High speed limiter register 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 Pulse count setting buffer lower 1 1 0 0 0 Pulse count setting buf...

Page 156: ...gister 1 0 0 0 1 Deviation over monitor register 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 Pulse count setting buffer lower 1 1 0 0 0 Pulse count setting buffer middle 1 1 0 0 1 Puls...

Page 157: ...Section 6 Parameters Registers Page 6 1 Parameters List Registers 6 1 6 2 Relationship between Parameters Registers 6 2 6 3 Detailed Description of Parameters Registers 6 4...

Page 158: ...a e R 3 1 o t 1 1 d e s u t o N t i b 0 4 1 r e t s i g e r r e m i t g n i r o t i n o m r o r r E 5 3 5 5 6 o t 0 s t i b 6 1 e t i r w d a e R 5 1 r e t s i g e r l o r t n o C 5 3 5 5 6 o t 0 s t...

Page 159: ...MP1 NP1F MP2 is calculated using the following formulas 1 When the effective bit length of the frequency register is 20 bits Output frequency kHz 25000kHz x Set value of frequency register 220 x 1 Set...

Page 160: ...eration deceleration register becomes as follows Acceleration deceleration time 220 1 25000kHz 2 1048576 1 25000kHz 2 83 9ms 2 When the effective bit length of the frequency register is 16 bits Accele...

Page 161: ...gister When data is written by selecting the target frequency register the speed setting is updated while the command pulse is being output Point of use This method requires some time for writing beca...

Page 162: ...L level active condition After this when a value other than zero is assigned to the target frequency register positioning at the target point will be completed normally Precautions o N r e t s i g e...

Page 163: ...y register is copied in this area When constant speed is reached after the end of acceleration deceleration the setting of this register becomes equal to that of the target frequency register or the b...

Page 164: ...the value of the target frequency register When data is written into the target frequency register the command pulse frequency changes stepwise When the deceleration and stop or quick stop command is...

Page 165: ...ommand pulse register Signed data is valid for the written data If the sign is reverse to the current operating direction the pulse will be output in the reverse direction after the currently executed...

Page 166: ...mmand pulse is output the deceleration point register is counted up by the command pulse during acceleration the counter is counted down during deceleration The counter is also counted down during dec...

Page 167: ...stopped it is necessary to reset the deceleration point register In the following cases the deceleration point register is reset When stopped due to error detection such as emergency stop error OT er...

Page 168: ...olution of the command pulse frequency is 16 bit 20 bit width with respect to maximum command frequency Precaution The write command from the CPU module into the speed multiplication register is enabl...

Page 169: ...ecaution Write command for the FIFO buffer is enabled only in the pulse generation mode o N r e t s i g e r r e t e m a r a P e m a n r e t s i g e r r e t e m a r a P e u l a v l a i t i n I e t i r...

Page 170: ...t e m a r a P e m a n r e t s i g e r r e t e m a r a P e u l a v l a i t i n I e t i r w d a e R 3 1 d e s u t o N d e n i f e d n U o N r e t s i g e r r e t e m a r a P e m a n r e t s i g e r r e...

Page 171: ...p n e h w d r a w r o F 1 3 d e s u t o N 0 e b t s u M 4 d e s u t o N 0 e b t s u M 5 t c e l e s e p y t l a n g i s e s l u p l a n r e t x E 0 9 0 e s l u p B e s a h p A e s a h p l a n g i s l...

Page 172: ...es in the forward direction when phase B is advanced Phase B feedback pulse Phase A feedback pulse Time When the motor is rotating in the forward direction phase B changes first Motor rotating in forw...

Page 173: ...reatment by OT detection is performed if OT input signal is turned OFF NC contact signal When OT detection is disabled the OT signal can be used as a general purpose input signal 6 Automatic accelerat...

Page 174: ...et to 1 NO contact input Input is ON when external contact is closed Point of use When the origin LS signal is ON phase Z detection is not performed 9 Phase Z signal input level bit 11 Selects the inp...

Page 175: ...cklash pulses in the range from 0 to 2047 The setting of the backlash register can be used in all modes o N r e t s i g e r r e t e m a r a P e m a n r e t s i g e r r e t e m a r a P e u l a v l a i...

Page 176: ...imit value for frequency register setting data In the position command mode works as the upper limit value for the increment of pulse count per millisecond o N r e t s i g e r r e t e m a r a P e m a...

Page 177: ...e lower 20 bits of 2 words in the set value data area are used as speed data For writing in the pulse count setting buffer the remaining 12 bits of the set value data area are used a Pulse count setti...

Page 178: ...into the pulse count setting buffer is enabled only in the pulse generation mode o N r e t s i g e r r e t e m a r a P e m a n r e t s i g e r r e t e m a r a P e u l a v l a i t i n I e t i r w d a e...

Page 179: ...to be added in the comm and pulse register becomes 0 When a value which exceeds one word 65535 pulses is to be added use pulse count setting buffer upper middle and lower Sample pulse output at 250kH...

Page 180: ...enabled in position command mode Delay time can be set in 0 1ms steps maximum value is 25 5ms Set delay time in the following manner Delay time Tact time ms x SX bus transmission times 1 3 0 x 10 SX b...

Page 181: ...otion 7 16 2 When SOT software OT is disabled for infinite length motion 7 16 7 3 12 Original point return motion 7 17 7 3 13 Positioning operation 7 18 7 3 14 Interrupt point positioning motion 7 19...

Page 182: ...s been detected 7 36 7 4 8 Operation when an OT error has been detected 7 36 7 4 9 Operation when a transmission error has been detected 7 36 7 4 10 Operation for resetting deviation 7 37 7 4 11 Backl...

Page 183: ...bed below 1 Pulse generation mode Positioning is performed based on moving length the number of output pulses and the setting of the target frequency Point of use The number of output pulses and the t...

Page 184: ...and pulse signal is selected Points of use When Feedback Pulse Select is disabled the command pulse signal is input to the deviation counter as a command pulse as well as feedback pulse Therefore in t...

Page 185: ...e following items from the CPU module 1 Moving length the number of output pulses 2 Target frequency 2 Position command mode This mode is used to set the following item from the CPU module 1 Position...

Page 186: ...5 1 7 P 0 1 3 7 h p a r g a r a P n o i t a r e p o l a u n a M 6 1 7 P 1 1 3 7 h p a r g a r a P n o i t o m n r u t e r t n i o p l a n i g i r O 7 1 7 P 2 1 3 7 h p a r g a r a P n o i t a r e p o...

Page 187: ...mmand data sent from the CPU module Frequency data is set in the target frequency register FIFO buffer or set value data area 3 Pulse generator Outputs the command pulses for positioning 4 Deviation c...

Page 188: ...reset Read data Command pulse zero Most significant bit The pulse train positioning control combined module outputs current command values into the current command value data area Point of use When t...

Page 189: ...2 Calculation of command frequency for 20 bit length Command frequency 25 000kHz x 1 Set value of speed multiplication register 1 x Set value of frequency register 1048576 x 1 2 Point of use Because...

Page 190: ...point is detected Base frequency register Current frequency register Count up acceleration Base frequency register Current frequency register Count down deceleration Base frequency register Current fr...

Page 191: ...nd frequency Acceleration deceleration time is the time until the target frequency is reached from speed 0 Therefore the acceleration time from 0 to 250kHz becomes as follows 20 bit width when target...

Page 192: ...ster is counted down according to the command pulse Comparing the command pulse register the remaining number of output pulses with the deceleration point register operation is decelerated from the po...

Page 193: ...is the same as in automatic calculation Namely the command pulse register is counted down according to the command pulse The command pulse register the remaining number of output pulses is compared w...

Page 194: ...ata area into the target frequency register Frequency Time Frequency 3 Frequency 1 Frequency 2 Frequency 2 Frequency 1 Frequency 3 1 1 Set value data PC MP1 MP2 Speed change command PC MP1 MP2 Speed c...

Page 195: ...gister Command pulse register 1 1 Register select PC MP1 MP2 Write command PC MP1 MP2 Frequency data Pulse count data Set value data PC MP1 MP2 1 1 Response to write command PC MP1 MP2 Point of use Th...

Page 196: ...MP2 1 1 Response to read command PC MP1 MP2 Points of use This module NP1F MP1 NP1F MP2 outputs response signal to the read command sent from the CPU module By the response to read command handshaking...

Page 197: ...dback pulse phase B Phase Z signal Interrupt detection latch 16 bit Data latch Interrupt detected position Interrupt Current value counter is a 32 bit length ring counter for counting up down Current...

Page 198: ...stop manual operation use the deceleration and stop command SOT SOT Current position Pm For manual forward operation set the pulse count which corresponds to Pp in the command pulse register For manua...

Page 199: ...he number of pulses which is set in the command pulse register will be output Set value of the command pulse register the shift length to original point f H Frequency Time f L 1 Interrupt mode PC MP1...

Page 200: ...f the value to be added is set to 0 an overrun occurs passing the target position when stopped In such cases decrease the creep speed 7 3 13 Positioning operation Write the necessary data in each regi...

Page 201: ...ioning end PC MP1 MP2 1 Command pulse zero PC MP1 MP2 Not accepted because interrupt detect command is 0 Points of use If only shift length is specified for positioning at interrupt by the servo syste...

Page 202: ...the completion of pulse output by the command pulse register 0 is given priority Acceleration deceleration register 1 n2 Data m Detection of completion Current frequency 20 bit Up down counter Compar...

Page 203: ...tion r egister 1 1 Start command PC MP1 MP2 Released EMG external input 1 Emergency stop error PC MP1 MP2 1 1 Positioning end PC MP1 MP2 0 Command pulse zero PC MP1 MP2 The data for the remaining numb...

Page 204: ...o increase the counter value is output Even during OT error detection the reverse pulse train command can be used An OT error can be detected only when a reverse command pulse in the direction to decr...

Page 205: ...and PC MP1 MP2 Positioning end PC MP1 MP2 Sign select PC MP1 MP2 OT external input OT error external input OT error PC MP1 MP2 OT external input Released Released 0 forward 1 1 1 reverse 1 The positio...

Page 206: ...Hz 131ms When phase Z or interrupt signal is detected this module NP1F MP1 MP2 calculates the deviation amount on the servo amplifier side from the command pulse counter value and detected position da...

Page 207: ...on error PC MP1 MP2 Frequency Time Acceleration deceleration register 2 Pattern when positioning is performed normally Acceleration deceleration register 1 1 Released 1 1 1 0 The data for the remainin...

Page 208: ...er data is a constant speed motion except interrupt positioning When the interrupt mode is selected operation is stopped once at the preceding step Operation is then resumed in interrupt mode When the...

Page 209: ...zero signal and near zero signal are used to detect the completion of operation When the start command is 0 the data written in the FIFO buffer are stored as unexecuted data in order When the buffer...

Page 210: ...ts of 2 word data 32 bits in set value data area 2 are used With pulse setting buffer lower register select 24 the data of the remaining 12 bits is added to the command pulse register as pulse count d...

Page 211: ...e multiplication becomes as follows x1 For one feedback pulse multiplied by 4 x2 For 2 feedback pulses multiplied by 2 x4 For 4 feedback pulses multiplied by 1 On the module side NP1F MP1 MP2 the disp...

Page 212: ...x 1 x t n u o c e s l u p t u p t u O 1 x 1 x 1 x y c n e u q e r f t u p t u O 1 x 1 x 1 x This module NP1F MP1 MP2 multiplies feedback pulses by 4 This module NP1F MP1 MP2 controls position by the a...

Page 213: ...e b s a h r o r r e p o t s y c n e g r e m e n a n e h w n o i t a r e p O 6 3 7 P 7 4 7 h p a r g a r a P n a n e h w n o i t a r e p O d e t c e t e d n e e b s a h r o r r e T O 6 3 7 P 8 4 7 h p...

Page 214: ...value Previous set value Increment is calculated each time data is received from the CPU module 3 Calculation of set value The data which is to be set in the target frequency register is calculated T...

Page 215: ...ng is executed using delay time In the position command mode the number of pulses which are to be output for the unit time period as well as the frequency are automatically calculated and set from the...

Page 216: ...rement is added to the pulse increment of the next cycle Limiter value is processed as the upper limit for the pulse increment per millisecond Namely it is 1 000 pulses equivalent to 1MHz or the set v...

Page 217: ...s added Po Psv Ppv to the command position becomes the original point When the total increase of command position since the rising edge of the start signal becomes Po Ppv holding the command position...

Page 218: ...An OT error is detected when Increase of position data sent from the CPU module 0 An OT error is not detected while Increase of position data 0 An OT error is also not detected when the start command...

Page 219: ...r Motor PG Feedback pulse Servo amplifier On the servo amplifier side command pulse multiplication x1 x2 x4 is set According to the set multiplication the number of revolutions of motor per single com...

Page 220: ...x 1 x t n u o c e s l u p t u p t u O 1 x 1 x 1 x y c n e u q e r f t u p t u O 1 x 1 x 1 x Precautions This module NP1F MP1 MP2 multiplies feedback pulses by 4 This module NP1F MP1 MP2 controls the p...

Page 221: ...n counter counts pulses in the range between 32676 and 32676 The current value of the up down counter is continuously output in the external pulse input counter area 90 phase differential signal phase...

Page 222: ...the CPU module has ended Completion of transmission from SX bus t 11 t 01 t 02 T Constant period timer of this module P 1 P 0 t 01 to t 11 Detection time Detection time is updated whenever constant pe...

Page 223: ...Section 8 Troubleshooting Page 8 1 LED Indication 8 1 8 2 Error Indication 8 2...

Page 224: ...ng control combined module NP1F MP2 LED indication green or red 1 ONL RDY EMG ERR ALM OT OT CH1 CH2 20 1 B A CH2 CH1 1 For error indication LEDs are used as follows ONL green ERR red RDY green ALM red...

Page 225: ...urned on ERR LED On ALM LED On ONL LED Blinking Occurred because there is no terminating plug Cause Mount the terminating plug Turn the power on again For this terminating plug NP8B BP is necessary Re...

Page 226: ...was turned on 1 Positioning control module RDY LED Blinking ALM LED Blinking 2 CPU module ERR LED On ALM LED On 3 I O module ONL LED Blinking Internal memory of the positioning control module is abnor...

Page 227: ...er was turned on 1 Positioning control module RDY LED Off ALM LED Blinking 2 CPU module ERR LED On ALM LED On 3 I O module ONL LED Blinking Internal memory of the positioning control module is abnorma...

Page 228: ...the power was turned on 1 Positioning control module RDY LED Off ALM LED Off 2 CPU module ERR LED On ALM LED On 3 I O module ONL LED Blinking CPU of the positioning control module is abnormal Cause R...

Page 229: ...le ERR LED Off RUN LED On ALM LED On 3 I O module ONL LED On The set value of the parameter for deviation over detection is too small Mechanical braking force is acting on the motor shaft Motor does n...

Page 230: ...e RDY LED On ALM LED On 2 CPU module ERR LED Off ALM LED On 3 I O module ONL LED On Problem occurred in the user application software The positioning control module is abnormal Cause Correct the user...

Page 231: ...D Off EMG LED On OT LED On OT LED On 2 CPU module ERR LED Off ALM LED Off ONL LED On RUN LED On 3 I O module ONL LED On ERR LED Off Power is not supplied to the positioning control module external 24V...

Page 232: ...OT LED Off 2 CPU module ONL LED On ERR LED Off RUN LED On ALM LED Off 3 I O module ONL LED On ERR LED Off Wrong wiring User program error Servo amplifier is off line Servo amplifier requires special...

Page 233: ...5 Terminology App 12 1 Absolute positioning App 12 2 Incremental positioning App 12 3 Zero point return App 12 4 0 near zero App 12 5 Dwell timer App 12 6 M code App 12 7 Override speed App 13 8 Devia...

Page 234: ...e s u t o N d e n i f e d n U 2 1 d e s u t o N d e n i f e d n U 3 1 d e s u t o N d e n i f e d n U 4 1 r e t s i g e r r e m i t g n i r o t i n o m r o r r E 5 3 5 5 6 o t 0 s t i b 6 1 0 5 1 r e...

Page 235: ...g r a T O 0 1 r e f f u b O F I F e s l u p d n a m m o C O 1 1 d e s u t o N 2 1 d e s u t o N 3 1 d e s u t o N 4 1 r e t s i g e r r e m i t g n i r o t i n o m r o r r E O O 5 1 r e t s i g e r l...

Page 236: ...o c e u l a v t n e r r u c o t e s n o p s e R O O 5 d e e p s g n i g n a h C O 6 n o i t c e t e d l a n g i s Z e s a h P O O 7 n o i t c e t e d n o i t i s o p t p u r r e t n I O O 8 e t o N d...

Page 237: ...s e R O O 2 1 o t 8 r e t s i g e r y c n e u q e r f t e g r a T O O r e t s i g e r y c n e u q e r f e s a B O r e t s i g e r y c n e u q e r f t n e r r u C O O r e t s i g e r e s l u p d n a m...

Page 238: ...v e D O O r e t s i g e r r e t i m i l d e e p s h g i H O O d e s u t o N d e s u t o N d e s u t o N d e s u t o N r e w o l g n i t t e s t n u o c e s l u P O e l d d i m g n i t t e s t n u o c...

Page 239: ...n e r r u C O O 5 d n a m m o c e g n a h c d e e p S O 6 d n a m m o c t c e t e d l a n g i s Z e s a h P O O 7 t c e t e d n o i t i s o p t p u r r e t n I O O 8 e d o m t p u r r e t n I O 9 e t...

Page 240: ...t o N r e t s i g e r r e m i t g n i r o t i n o m r o r r E r e t s i g e r l o r t n o C O O r e t s i g e r h s a l k c a B O O r e t s i g e r g n i r o t i n o m o r e z r a e N O O r e t s i g...

Page 241: ...O F I F e s l u p d n a m m o C O d e s u t o N d e s u t o N d e s u t o N r e t s i g e r r e m i t g n i r o t i n o m r o r r E O O r e t s i g e r l o r t n o C O O r e t s i g e r h s a l k c a...

Page 242: ...n o i t c e t e d T O O O 7 e l b a s i d n o i t c e t e d T O O O 8 e l b a s i d n o i t a r e l e c e d n o i t a r e l e c c a c i t a m o t u A O 9 e l b a s i d n o i t a l u c l a c t n i o p...

Page 243: ...urrent external pulse data read Current command value read Current command value read 10 Bit command signal 11 Bit command signal 12 Set value area 13 Set value area lower word PC MP1 upper word PC MP...

Page 244: ...odule detection time P 14 Ch1 Bit command signal 15 Ch1 Bit command signal 16 Ch1 Set value 17 Ch1 Set value 18 Ch2 Bit command signal 19 Ch2 Bit command signal 20 Ch2 Set value 21 Ch2 Set value upper...

Page 245: ...2000 1000 is set as the position data 3 Zero point return When accurate positioning is required it is necessary to accurately set the reference point original point Original point return is the opera...

Page 246: ...er the shock acting on the mechanical system while the motor is accelerated and thus achieve smooth acceleration deceleration 11 Servo lock When the motor is stopped an external force may act resultin...

Page 247: ...e t w e r c S 1 P 9 0 T 2 3 Y 1 P N 2 3 1 e t o N s s e l r o A m 5 4 s d r o w 2 g 0 3 1 x o r p p A e p y t r o t c e n n o C 2 e t o N 1 P 9 0 T 4 6 Y 1 P N 4 6 1 e t o N s s e l r o A m 0 9 s d r...

Page 248: ...S R s s e l r o A m 0 1 1 g 0 7 1 x o r p p A e p y t r o t c e n n o C 2 S R L 1 P N 1 x C 2 3 2 S R s s e l r o A m 0 9 g 0 6 1 x o r p p A e p y t r o t c e n n o C 4 S R L 1 P N 1 x 5 8 4 S R s s...

Page 249: ...1 M M F 1 P N 1 s s e l r o A m 0 2 1 g 0 0 2 x o r p p A 6 0 S B 1 P N s s e l r o A m 5 4 g 0 2 4 x o r p p A 8 0 S B 1 P N s s e l r o A m 0 5 g 0 4 5 x o r p p A 1 1 S B 1 P N s s e l r o A m 0 6...

Page 250: ...Gate City Ohsaki East Tower 11 2 Osaki 1 chome Shinagawa ku Tokyo 141 0032 Japan Phone 81 3 5435 7135 8 Fax 81 3 5435 7456 9 URL http www fujielectric co jp kiki Information in this manual is subject...

Reviews: