6.4 Local adjustment from the digital display
In nuclear power plants, all on site modifications of the configuration of the FCX-AII
transmitters may only be done with the aid of the mobile communicator.
1. Description
If the transmitter is equipped with a numerical indicator, the local adjustment on the FCX
transmitter-AII is possible without the use of the FXW mobile communicator.
The following switches are integrated on the digital indicator to perform the local settings:
Table 1- “Mode” switch functions
Switch
DAMP
Switch
MODE
LCD display
Switch
LOCAL/COMM.
Table 2- functions of the “Damp” switch
Transmitter DP
Adjustment of the zero by applying pressure
corresponding to an output signal of 4 mA
Adjustment of the scale by applying the
pressure corresponding to a linear output signal
of 20 mA
Locking of the local setting - Linear output
signal
Generation of the output signal at 4 mZ
Generation of the output signal at 12 mA
Generation of the output signal at 20 mA
Adjustment of the scale by applying the
pressure corresponding to an output signal
√ 20 mA
Locking the local setting - output signal √
Position
0
1
2
3
4
5
6
7
Functions
Zero
adjustment
Adjustment
of the linear
output signal
scale
Locking
Locking 4 mA
Locking
Adjustment 20 mA
Adjustment
of the scale
output signal √
Locking
Transmitter GP and AP
Zero adjusment by applying the pressure
corresponding to an output signal of 4 mA
Adjustment of the scale by applying the pressure
corresponding to a linear output signal of 20 mA
Locking of the local setting - Linear output signal
Generation of the output signal at 4 mZ
Generation of the output signal at 12 mA
Generation of the output signal at 20 mA
Adjustment of the scale by applying the pressure
corresponding to a linear output signal of 20 mA
Locking the local setting - linear output signal
Table 3. LOCAL/COMM. switch
Position of the switch
Possible settings
LOCAL
Local settings using the “MODE” and “DAMP” switch.
COMM.
Adjustment of the transmitter with FXW or UHI 275 mobile communicator
Position of
Additional time
switch
(sec.)
0
0
1
0.3
2
0.6
3
1.2
4
2.4
5
4.8
6
9.6
7
19.2