32
TN4FCXA2
j
-EDF-
E
10.5 ~ 45 V DC (Analogique)
16.1 ~ 45 V DC (Smart)
Sortie courant 4 ~ 20mA
Bornier
CK
+
CK
–
+
–
Convertisseur
10.5 ~ 45 V DC (Analogique)
16.1 ~ 45 V DC (Smart)
Sortie 4 ~ 20mA
4 ~ 20mA DC
–
+
Convertisseur
CK
+
CK
–
+
–
Connection diagram of the terminal.
Tighten the terminal block screws (M4x10) to a torque of
approximately 1.5 N.m
After the wiring, correctly retighten the cover so that it
cannot be unscrewed.
Use of a remote indicator
To directly connect a remote indicator, it must link the “
+
”
and the “
-
” of the latter respectively to the CK+ and CK-
terminals of the transmitter as indicated on the diagram.
4.1 Wiring procedure:
Sealing of cable passage
The cable passage depends on the order, see the technical specification for different possibilities
and dimensions.
Avoid the use of a metal tube to protect the cable if the inlet is at the top,
because this encourages the accumulation of water at the cable inlet of
the transmitter, and increases the risk of water getting into the transmitter.
Check that the threading of cable routing corresponds to that of mounting
accessories used
INDICATION
Cable
Tube
métallique