Connection instructions.
(1) Measurement of gas pressure.
The pressure intake must be located
in the upper part of the piping and the
separator above it.
Isolating valve
Pressure reading
connector
Venting into
atmosphere
Transmitter
Separator
Piping
It is recommended that the pressure transmitter be installed below the
separators. If the pressure of the process is less than the atmospheric
pressure, this becomes essential.
Vibrations on the capillaries can create interference with the measurement
and distort it. It is therefore advisable to install the transmitter on a vibration-
free bracket and to attach the capillaries to stable structures.
(3) Level measurement in an open tank.
H
1
must be greater than the half
diameter of the measurement
membrane of the separator flange.
If this is not the case, the measure
would not be proportional to the level
as long as the membrane is not totally
immersed.
Transmitter
Separator
Isolating valve
max.
level
Pressure reading
connector
Separator
Isolating valve
Venting into
atmosphere
Piping
(2) Measurement of liquid pressure.
The pressure intake must be located
in the lower part of the piping and the
separator below it.
Transmitter
INTERDICTION