7.4 Settings that must be carried out after replacement of the amplifier or
the cell
Settings
After complete assembly of the transmitter, follow the following steps to adjust and calibrate the
device. This must be done with the FXW mobile communicator.
(1) After replacement of the amplifier
Step
settings
See page
1
Calibration of the converter
P.29-30
Digital/Analogue
2
Tag
P.42
3
Type of transmitter
P.42
4
Physical units
P.44
5
Regulation of zero and measuring range
P.45
6
Calibration of zero and measuring range
P.45
7
Damping
P.46
8
Linear/square root output function
P.47
9
Output signal in the event of defect
P.48
10
Locking of the external adjustment
P.52
(2) After replacement of the whole cell
Step
Setting
See page
1
Adjustment of the zero and the measuring range
45