TROUBLESHOOTING
18-24k Diagnosis of overload and discharge malfunction
Diagnosis for overload and discharge malfunction (AP1 below is control board of outdoor unit)
Main detection point:
Malfunction diagnosis process:
●
If the electron expansion valve is connected well? Is the expansion valve damaged?
●
If the refrigerant is leakage?
●
If the overload protector is damaged?
Connect wire
well with wiring
diagram
Replace EKV
coil of electron
expansion valve
Remove
malfunction?
After the unit
for 20min
de-energized
Remove
malfunction?
The resistance value of
firs t 4 l ead fo ot an d th e
fif th lead foot is similar,
less than 100
Y
If the wiring terminal FA of electron
expansion is well connected?
Y
N
N
N
If the overload protector SAT
is well connected?
N
Under ambient temperature, test the
resistance of overload protector with ohmic
Y
Replace
overload
protector SAT
N
Y
Replace
Check refrigerant, if there is
leakage, please refer to
specification
control board
AP1
End
Summary of Contents for FSHW091
Page 8: ...8 INTRODUCTION FSHSW09A1A FSHSW12A1A Figure 102 Indoor Units FSHSW18A3A FSHSW24A3A FSHSW36A3A ...
Page 47: ...47 INSTALLATION ...
Page 48: ...48 INSTALLATION Installation Tools ...
Page 72: ...72 WIRED CONTROLLER Display ...
Page 122: ...122 TROUBLESHOOTING Malfunction of IDUFanMotorU8 Service Manual No Start End ...
Page 146: ...146 WIRING DIAGRAMS Figure 8054 9 12KOutdoorUnitWiringDiagrams 60000706067401 3 2 N 1 C3 C4 ...
Page 158: ...158 FIgure 906 PARTS CATALOG 9KOutdoorUnit 28 27 29 31 30 32 ...
Page 160: ...160 PARTS CATALOG 12k OutdoorUnit 28 27 29 31 30 32 FIgure 907 ...