44
PB
OPERATION
36k Sequence of Operation
2) Heating overload
c. If
Ttube ≥
136°F, the compressor will run at reduced frequency.
d. If
Ttube ≥
144°F, the compressor will stop and the indoor fan will run at preset speed.
a. If
Ttube ≤
126°F, the unit will return to its original operation state.
b. If
Ttube ≥
131°F, frequency rise is not allowed.
c. If
Ttube ≥
136°F, the compressor will run at reduced frequency.
d. If
Ttube ≥
144°F,the compressor will stop and the indoor fan will blow residue heat and then stop.
Designation of sensors
Faults
Indoor ambient temperature
The sensor is detected to be open-circuited or short-circuited for successive 5
seconds
Indoor tube temperature
The sensor is detected to be open-circuited or short-circuited for successive 5
seconds
Outdoor ambient temperature
The sensor is detected to be open-circuited or short-circuited for successive 30
seconds
Outdoor tube temperature
The sensor is detected to be open-circuited or short-circuited for successive 30
seconds, and no detection is performed within 10 minutes after defrost begins.
Exhaust
After the compressor has operated for 3 minutes, the sensor is detected to be
open-circuited or short-circuited for successive 30 seconds.
Overload
After the compressor has operated for 3 minutes, the sensor is detected to be
open-circuited or short-circuited for successive 30 seconds.
②
Exhaust temperature protection of compressor
If exhaust temperature ≥
208°F, frequency is not allowed to rise.
If exhaust temperature ≥
217°F, the compressor will run at reduced frequency.
If exhaust temperature ≥
230°F, the compressor will stop.
If exhaust temperature ≤ 194°
F, the compressor has stayed at stop for at least 3 minutes, the compressor will resume its operation.
③
Communication fault
④
Module protection
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, the compressor will
resume its operation. If module protection occurs six times in succession, the compressor will not be started again.
⑤
Overload protection
If temperature sensed by the overload sensor is over
239
°F, the compressor will stop and the outdoor fan will stop with a time lag of 30
seconds. If temperature is below 203°F, the overload protection will be relieved.
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a timelag of 30 seconds.
When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least 3 minutes, the compressor will
resume its operation.
⑥
Faults of temperature sensors
Summary of Contents for FSHW091
Page 8: ...8 INTRODUCTION FSHSW09A1A FSHSW12A1A Figure 102 Indoor Units FSHSW18A3A FSHSW24A3A FSHSW36A3A ...
Page 47: ...47 INSTALLATION ...
Page 48: ...48 INSTALLATION Installation Tools ...
Page 72: ...72 WIRED CONTROLLER Display ...
Page 122: ...122 TROUBLESHOOTING Malfunction of IDUFanMotorU8 Service Manual No Start End ...
Page 146: ...146 WIRING DIAGRAMS Figure 8054 9 12KOutdoorUnitWiringDiagrams 60000706067401 3 2 N 1 C3 C4 ...
Page 158: ...158 FIgure 906 PARTS CATALOG 9KOutdoorUnit 28 27 29 31 30 32 ...
Page 160: ...160 PARTS CATALOG 12k OutdoorUnit 28 27 29 31 30 32 FIgure 907 ...