112
PB
No.
Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor Unit
A/C status
Possible Causes
Dual‑8
Code
Display
Indicator Display (During blinking,
ON 0.5s and OFF 0.5s)
Indicator has 3 kinds of display status
and during blinking, ON 0.5s and
OFF 0.5s
Power
Indicator
Cool
Indicator
Heating
Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
14
outdoor
ambient
temperature
sensor is
open/ short
circuted
F3
OFF 3s
and blink
3 times
OFF 1s
and blink 6
times
During cooling and drying
operating, compressor stops
while indoor fan operates;
During heating operation,
the complete unit will stop
operation
Outdoor temperature sensor
hasnt’ been connected well or
is damaged. Please check it
by referring to the resistance
table for temperature sensor)
15
outdoor
condenser
temperature
sensor is
open/ short
circuted
F4
OFF 3s
and blink
4 times
OFF 1s
and blink 5
times
During cooling and drying
operation, compressor stops
while indoor fan will operate;
During heating operation,
the complete unit will stop
operation.
Outdoor temperature sensor
hasnt been connected well or
is damaged. Please check it
by referring to the resistance
table for temperature sensor
16
outdoor
discharge
temperature
sensor is
open/ short
circuted
F5
OFF 3s
and blink
for 5
times
OFF 1S
and blink 7
times
During cooling and drying
operation, compressor will
sop after operating for about
3 mins,
while indoor fan will operate;
During heating operation, the
complete unit will stop after
operating for about 3 mins.
1. Outdoor temperature sen‑
sor hasnt been connected well
or is damaged. Please check it
by referring to the resistance
table for temperature sensor
2. The head of temperature
sensor hasnt been inserted
into the copper tube
17
limit/
decrease fre‑
quency due to
overload
F6
OFF 3s
and blink
for 6
times
OFF 1s
and blink 3
times
All loads operate normally,
while
operation frequency for
compressor is decreased
Refer to the malfunction
analysis (overload, high
temperature resistant)
18
decrease fre‑
quency due to
overcurrent
F8
OFF 3s
and blink
8 times
OFF 1s
and blink
once
All loads operate normally,
while
operation frequency for
compressor is decreased
The input supply voltage is too
low; System pressure is too
high and overload
19
decrease
frequency
due to high
air discharge
F9
OFF 3s
and blink
9 times
OFF 1s
and blink
twice
All loads operate normally,
while
operation frequency for
compressor is decreased
Overload or temperature is
too high; refrigerant is insuf‑
ficent Malfunction of electric
expansion valve (EKV)
20
limit/
decrease fre‑
quency due to
antifreezing
FH
OFF 3s
and blink
2 times
OFF 3s
and blink 2
times
OFF 1s
and blink 4
times
All loads operate normally,
while operation frequency for
compressor is decreased
Poor air‑return in indoor unit
or fan speed is too low
TROUBLESHOOTING
Diagnostic Codes
Summary of Contents for FSHW091
Page 8: ...8 INTRODUCTION FSHSW09A1A FSHSW12A1A Figure 102 Indoor Units FSHSW18A3A FSHSW24A3A FSHSW36A3A ...
Page 47: ...47 INSTALLATION ...
Page 48: ...48 INSTALLATION Installation Tools ...
Page 72: ...72 WIRED CONTROLLER Display ...
Page 122: ...122 TROUBLESHOOTING Malfunction of IDUFanMotorU8 Service Manual No Start End ...
Page 146: ...146 WIRING DIAGRAMS Figure 8054 9 12KOutdoorUnitWiringDiagrams 60000706067401 3 2 N 1 C3 C4 ...
Page 158: ...158 FIgure 906 PARTS CATALOG 9KOutdoorUnit 28 27 29 31 30 32 ...
Page 160: ...160 PARTS CATALOG 12k OutdoorUnit 28 27 29 31 30 32 FIgure 907 ...