TROUBLESHOOTING
Diagnostic Codes
No.
Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor Unit
A/C status
Possible Causes
Dual‑8
Code
Display
Indicator Display (During blinking,
ON 0.5s and OFF 0.5s)
Indicator has 3 kinds of display status
and during blinking, ON 0.5s and
OFF 0.5s
Power
Indicator
Cool
Indicator
Heating
Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
9
Limit/
decrease
frequency
due to high
temperature
EU
OFF 3s
and blink
6 times
OFF 3s
and blink
6 times
All loads operate normally,
while
operation frequency for
compressor is decreased
Discharging after the
complete unit is de‑energized
for 20mins, check whether
the thermal grease on IPM
Module of outdoor control
the radiator is inserted tightly.
If its no use, please replace
control panel AP1.
10
Malfunction
protection of
jumper cap
C5
OFF 3s
and blink
15 times
Wireless remote receiver
and button are effective, but
can not dispose the related
command
1.No jumper cap insert on
mainboard.
2.Incorrect insert of jumper
cap.
3.Jumper cap damaged.
4.Abnormal detecting circuit of
mainboard.
11
Gathering
Refrigerant
F0
OFF 3s
and blink
once
OFF 3s
and blink
once
OFF 1s
and blink
17 times
When the outdoor unit receive
signal of Gathering refrigerant
,the system will be forced to
run under cooling mode for
gathering refrigerant
Nominal cooling mode
12
Indoor ambi‑
ent tempera‑
ture sensor is
open/ short
circuited
F2
OFF 3s
and blink
once
During cooling and drying
operation, indoor unit oper‑
ates while other loads will
stop; during heating operation,
the complete unit will stop
operation.
1.Loosening or bad contact of
indoor ambient temp. sensor
and mainboard terminal.
2.Components in mainboard
fell down leads short circuit.
3.Indoor ambient temp.
sensor damaged.(check with
sensor resistance value chart)
4.Mainboard damaged.
13
indoor
evaporator
temperature
sensor is
open/ short
circuted
F2
OFF 3s
and blink
twice
AC stops operation once
reaches the setting tempera‑
ture. Cooling, drying: internal
fan motor stops operation
while other loads stop
operation; heating: AC stop
operation
1.Loosening or bad contact
of Indoor
evaporator temp. sensor and
mainboard terminal.
2.Components on the
mainboard fall down leads
short circuit
3.Indoor evaporator temp.
sensor damaged.(check temp.
sensor value
chart for testing)
4.Mainboard damaged.
Summary of Contents for FSHW091
Page 8: ...8 INTRODUCTION FSHSW09A1A FSHSW12A1A Figure 102 Indoor Units FSHSW18A3A FSHSW24A3A FSHSW36A3A ...
Page 47: ...47 INSTALLATION ...
Page 48: ...48 INSTALLATION Installation Tools ...
Page 72: ...72 WIRED CONTROLLER Display ...
Page 122: ...122 TROUBLESHOOTING Malfunction of IDUFanMotorU8 Service Manual No Start End ...
Page 146: ...146 WIRING DIAGRAMS Figure 8054 9 12KOutdoorUnitWiringDiagrams 60000706067401 3 2 N 1 C3 C4 ...
Page 158: ...158 FIgure 906 PARTS CATALOG 9KOutdoorUnit 28 27 29 31 30 32 ...
Page 160: ...160 PARTS CATALOG 12k OutdoorUnit 28 27 29 31 30 32 FIgure 907 ...