113
PB
No.
Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor Unit
A/C status
Possible Causes
Dual‑8
Code
Display
Indicator Display (During blinking,
ON 0.5s and OFF 0.5s)
Indicator has 3 kinds of display status
and during blinking, ON 0.5s and
OFF 0.5s
Power
Indicator
Cool
Indicator
Heating
Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
21
voltage for
DC bus bar is
too high high
PH
OFF 3s
and blink
11 times
OFF 1s
and blink
13 times
During cooling and drying op‑
eration, compressor will stop
while indoor fan will operate;
During heating operation,
the complete unit will stop
operation.
1.Measure the voltage of
position L and N on wiring
board (XT), if the voltage is
higher than 265VAC, turn
on the unit after the supply
voltage is increased to the
normal range.
2.If the AC input is normal,
measure the voltage of
electrolytic capacitor C on
control panel (AP1), if its
normal, theres malfunction for
the circuit, please replace the
control panel (AP1)
22
voltage of DC
bus‑ bar is
too low
PL
OFF 3s
and blink
21 times
OFF 1s
and blink
12 times
During cooling and drying op‑
eration, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
1.Measure the voltage of
position L and N on wiring
board (XT), if the voltage is
higher than 150VAC, turn
on the unit after the supply
voltage is increased to the
normal range.
2.If the AC input is normal,
measure the voltage of elec‑
trolytic capacitor C on control
panel (AP1), if its normal,
there is a malfunction for the
circuit, replace the control
panel (AP1)
23
compres‑
sor min
frequence in
test state
P0
during
blinking
ON 0.25s
and OFF
0.25s
during
blinking
ON 0.25s
and OFF
0.25s
Showing during nominal cool‑
ing or nominal heating test
24
compres‑
sor rated
frequence in
test state
P1
during
blinking
ON 0.25s
and OFF
0.25s
during
blinking
ON 0.25s
and OFF
0.25s
Showing during middle cool‑
ing or middle heating test
25
compressor
maximum
frequence in
test state
P2
during
blinking
ON and
0.25s and
OFF and
0.25s
during
blinking
ON and
0.25s and
OFF and
0.25s
Showing during max. cooling
or max. heating test
TROUBLESHOOTING
Diagnostic Codes
Summary of Contents for FSHW091
Page 8: ...8 INTRODUCTION FSHSW09A1A FSHSW12A1A Figure 102 Indoor Units FSHSW18A3A FSHSW24A3A FSHSW36A3A ...
Page 47: ...47 INSTALLATION ...
Page 48: ...48 INSTALLATION Installation Tools ...
Page 72: ...72 WIRED CONTROLLER Display ...
Page 122: ...122 TROUBLESHOOTING Malfunction of IDUFanMotorU8 Service Manual No Start End ...
Page 146: ...146 WIRING DIAGRAMS Figure 8054 9 12KOutdoorUnitWiringDiagrams 60000706067401 3 2 N 1 C3 C4 ...
Page 158: ...158 FIgure 906 PARTS CATALOG 9KOutdoorUnit 28 27 29 31 30 32 ...
Page 160: ...160 PARTS CATALOG 12k OutdoorUnit 28 27 29 31 30 32 FIgure 907 ...