141
PB
Possible Causes
Discriminating Method (Air conditioner Status) Troubleshooting
Malfunction of the IDU fan motor
The IDU fan motor can’t operate
Refer to troubleshooting for H6 for mainte‑
nance method in details
Malfunction of the ODU fan motor
The ODU fan motor can't operate
Refer to point 4 of maintenance method for
details
Malfunction of compressor
Compressor can't operate
Refer to point 5 of maintenance method for
details
Horizontal Louver Will Not Swing
Wrong wire connection, or poor connection
Check the wiring status according to circuit
diagram
Connect wires according to wiring diagram to
make sure all wiring terminals are connected
firmly
Stepping motor is damaged
Stepping motor can't operate
Repair or replace stepping motor
Main board is damaged
Others are all normal, while horizontal louver
can't operate
Replace the main board with the same model
ODU Fan Moto Can’t Operate
Wrong wire connection, or poor connection
Check the wiring status according to circuit
diagram
"Connect wires according to wiring diagram to
make sure all wiring terminals are connected
firmly"
Capacity of the ODU fan motor is damaged
"Measure the capacity of fan capacitor with
an universal meter and find that the capacity
is out of the deviation range indicated on the
nameplate of
fan capacitor."
Replace the capacity of fan
"Power voltage is a little low or
high"
"Use universal meter to measure the power
supply
voltage. The voltage is a little high or low"
Suggest to equip with voltage regulator
Motor of outdoor unit is damaged
"When unit is on, cooling/heating performance
is bad and ODU compressor generates a lot of
noise and heat."
Change compressor oil and refrigerant. If no
better, replace the compressor with a new one
Compressor Can’t operate
Wrong wire connection, or poor connection
Check the wiring status according to circuit
diagram
"Connect wires according to wiring diagram to
make sure all wiring terminals are connected
firmly"
Capacity of compressor is damaged
"Measure the capacity of fan capacitor with
an universal meter and find that the capacity
is out of the deviation range indicated on the
nameplate of
fan capacitor."
Replace the compressor capacitor
"Power voltage is a little low or
high"
"Use universal meter to measure the power
supply
voltage. The voltage is a little high or low"
Suggest to equip with voltage regulator
Coil of compressor is burnt out
"Use universal meter to measure the resis‑
tance
between compressor terminals and it's 0"
Repair or replace compressor
TROUBLESHOOTING
Troubleshooting for Malfunction without Active Error Code
Summary of Contents for FSHW091
Page 8: ...8 INTRODUCTION FSHSW09A1A FSHSW12A1A Figure 102 Indoor Units FSHSW18A3A FSHSW24A3A FSHSW36A3A ...
Page 47: ...47 INSTALLATION ...
Page 48: ...48 INSTALLATION Installation Tools ...
Page 72: ...72 WIRED CONTROLLER Display ...
Page 122: ...122 TROUBLESHOOTING Malfunction of IDUFanMotorU8 Service Manual No Start End ...
Page 146: ...146 WIRING DIAGRAMS Figure 8054 9 12KOutdoorUnitWiringDiagrams 60000706067401 3 2 N 1 C3 C4 ...
Page 158: ...158 FIgure 906 PARTS CATALOG 9KOutdoorUnit 28 27 29 31 30 32 ...
Page 160: ...160 PARTS CATALOG 12k OutdoorUnit 28 27 29 31 30 32 FIgure 907 ...