Chapter 7: Use the OTDR
The FaultMap Test
175
How to Do the FaultMap Test
Notes
The FaultMap test does not use the launch
compensation settings.
The FaultMap test uses the wavelength that gives
the best results.
Figure 69 shows the equipment for the FaultMap test.
1
Clean and inspect the connectors on the launch and tail cords
or patch cords and the link to be tested.
2
Connect the launch cord to the OTDR port and the link to be
tested, as shown in Figure 70. Connect a tail cord to the far
end of the link if necessary.
Or, you can use a patch cord that is 1 m long at minimum to
connect the tester to the link. To see results for the far-end
connector, connect a tail cord or patch cord (>1 m) to the far end
of the link.
3
On the home screen, tap the test setup panel.
4
On the
CHANGE TEST
screen, tap the button next to the
FaultMap
test, then tap
USE SELECTED
. If a FaultMap test is
not available, tap
NEW TEST
to add one to the project.
5
Tap
TEST
or press
.