
Versiv Cabling Certification Product Family
Users Manual
168
Overall Loss
: The loss of the cabling. This does not include the
OTDR connection and the loss of the last event. If
Launch
Compensation
is on, the overall loss includes the launch and
tail connectors, but not the launch and tail fibers.
If you did the test at two wavelengths, the tester shows the
highest loss of the two wavelengths.
N/A
shows for the
Overall Loss
if the tester cannot measure the
loss. This can occur when events are too close together or when
there is a large reflective event near the end of the fiber.
Fiber Length
: The length of the fiber. The units show in
meters (
m
) or feet (
ft
). If
Launch Compensation
is on, the
length does not include the length of the launch and tail
cords.
PASS/FAIL
: The overall result for the fiber.
PASS
: All measurements are within the test limits.
FAIL
: One or more measurements exceed the limit.
GPU22.EPS
Figure 66. EventMap Example 2
A
C
A
B
D
E
Summary of Contents for Versiv
Page 38: ...Versiv Cabling Certification Product Family Users Manual 24...
Page 86: ...Versiv Cabling Certification Product Family Users Manual 72...
Page 202: ...Versiv Cabling Certification Product Family Users Manual 188...
Page 214: ...Versiv Cabling Certification Product Family Users Manual 200...
Page 234: ...Versiv Cabling Certification Product Family Users Manual 220...
Page 244: ...Versiv Cabling Certification Product Family Users Manual 230...
Page 256: ...Versiv Cabling Certification Product Family Users Manual 242...
Page 258: ...Versiv Cabling Certification Product Family Users Manual 244...