Chapter 7: Use the OTDR
About Launch and Tail Cords
157
How to set up the launch compensation function
1
Select launch and tail cords that have the same type of fiber
as the fiber you will test.
2
On the home screen, tap the test setup panel. On the
CHANGE TEST
screen, select an OTDR test to change, then tap
EDIT
. Or to set up a new OTDR test, tap
NEW TEST
then tap
Auto OTDR
,
Manual OTDR
, or
DataCenter OTDR
.
3
On the
TEST SETUP
screen, tap the
Launch Compensation
control to set it to
On
.
4
On the
TEST SETUP
screen, make sure the
Fiber Type
is correct.
Change it if necessary.
5
On the
TEST SETUP
screen, tap
SAVE
.
6
On the home screen, tap the
TOOLS
icon, then tap
Set Launch
Compensation
.
7
On the
SET LAUNCH METHOD
screen tap the type of
compensation you want to do.
8
Clean and inspect the OTDR port and the launch/tail cord
connectors.
9
Make the connections for the type of compensation you
selected, as shown on the
SET LAUNCH METHOD
screen.
10
Tap
SET
.
11
When the
SET LAUNCH COMP
screen shows, select the event
or events that are the end of the launch cord and the start of
the tail cord (if you used a tail cord).
12
Tap
SAVE
.
Figure 68 shows an example of an OTDR trace with launch and
tail markers enabled.
Note
If you change the launch or tail cord, do the
compensation procedure again.
Summary of Contents for Versiv
Page 38: ...Versiv Cabling Certification Product Family Users Manual 24...
Page 86: ...Versiv Cabling Certification Product Family Users Manual 72...
Page 202: ...Versiv Cabling Certification Product Family Users Manual 188...
Page 214: ...Versiv Cabling Certification Product Family Users Manual 200...
Page 234: ...Versiv Cabling Certification Product Family Users Manual 220...
Page 244: ...Versiv Cabling Certification Product Family Users Manual 230...
Page 256: ...Versiv Cabling Certification Product Family Users Manual 242...
Page 258: ...Versiv Cabling Certification Product Family Users Manual 244...