Installation Instructions
16.1.09
Panda_6000i_System_eng_s01835.book.R01 - Chapter C: Installation Instructions Page 43
C.6 Installation of the fuel system
C.6.1 General references
Inside the generator capsule itself, there is the fuel filter installed (exception: Panda 4200 and
4500). Additional fuel filters (with water separator) must be mounted outside the capsule in easily
accessible places in the fuel lines between the tank intake fuel pump and the diesel motor's fuel
pump.
Generally forward and return fuel flow pipes must be mounted to the diesel tanks. Do not connect
the generator fuel supply lines with any other fuel lines of other diesel systems.
• The following items need to be installed:
• Fuel supply pump (12VDC)
• Pre-filter with water separator (not part of the delivery)
• Fine particle fuel filter
• Return fuel line to fuel tank (unpressurized)
The fuel supply pump should be mounted as close to the fuel tank as possible. The electric cable
for the fuel pump is already installed on the generator (length 5 m).
Fig. C.6.1-1: Installation scheme fuel system
1
2
3
4
5
8
7
6
1. Generator
2. Fuel stopcock
3. Fuel filter with water separator
4. Fuel return
5. Condensation water suction pump (option)
6. Fuel tank
7. Fuel supply
8. Electrical fuel pump (12V-DC)