Panda PMGi 6000
Page 100 - Chapter A: Panda PMGi 6000
PGMi 6000_eng.fm
Fischer Panda Datasheet
A.7 Cooling of the PMGi
Inside of the PMGi a fan is mounted.
Do not cover the air holes and grille.
The heat sink and the fan of the PMHGi may become dirty as a consequence of tzhe use of the generator, and so
the unit can loose a part of their heat transfer carateristic. Every 6 months it is necessary to visual inspect the heat
sinks and clean it with compressed air. At every Generator service the fan of the PMGi should be cleaned by the
special trained person.
A.8 Installation of the PMGi
The PMGi must be mounted vertical, with the electrical connection down. So you can read the writing on the
PMGi.
The surface where the PMGi is mounted should be smoothed and support the heat transfer. The Air holes and Air
grille must be not covered and enough cooling air must be pleasant at any time for the PMGi.
To mount the PMGi use the four fixing holes diameter 6,5mm.
Note! See the safety instruction in your Generator and iControl Manual.
The rules of the respective regional authority must be adhered to. Only an electrician may carry
out installation of the electrical connections for safety reasons.
A.8.1 Electrical connection.
Only special trained persons are allowed to make the electrical connection.
When an extension cable is required, be sure to use a though rubber sheated flexible and fireproof cable. Limit
length of extension cables depends on the voltage drop along the cable. This drop must be less than 2,5% value
of the nominal output voltage.
Pay attention to the right pin assignment. See “Socket pins of the PMGi 6000” on page 97.