Page 88 - Chapter A: Panda iControl
Panel_iControl_eng.fm
Fischer Panda Datasheet
Following warnigs are displayed
A.6 Error warnings
Error warnings are shown in the display. The screen switch from the temperature to „High“.
Engine temp.
> 75 °C
Exhaust temp.
> 70 °C
Winding temp.
> 120 °C
Table 1: Warning table
Example for the warning on the display
(Winding temp. „HIGH“)
Fig. A.6-1: Display warning (winding temp „high“) - example
A.7 Errors
The least 5 errors are stored in the electronic memory and can be read out by the service technican..
Push the „enter“ button to quitt errors which has stopped the generator
Unexpected stop
Generator stops during operation or RPM droped under 1100 RPM (Fuel low, overload
ect.)
Fault: Oilpress
Oilpressure to low
Fault: Winding
Winding temp. over 135°C
Fault: Exhaust
Exhaust tem over> 75°C (PMS version) or>100°C(vehicles versions)
Fault: Cyl. Head
Cylinder head temp. over >90°C (PMS version) or >95°C (vehicles versions)
Starting Fail
Generator do not start after 10 sec.
Table 2: Fault table