Reporting
SIA– FCP-75 Panel Communicator:
4.
When Reporting-by-Point is enabled, the communicator uses a “pi” event to supersede the actual point event to report the module to
which the point is linked.
5.
The Panel ID is not sent in the SIA Event Parameters.
11.3 SIA– FCP-75 Panel
Communicator:
(Differences/additional features are underlined).
The Events are sent to the Central Station Receiver as a fixed length string:
The Event Format is:
EEPPMMZZZZ
Where the Event Format is defined as follows:
1.
The Event field will contain 10 digits including the 2 digit Event Code (EE), 2 digit panel ID (PP), 2 digit Module Number (MM) and a
4 digit Event Parameter (ZZZZ).
2.
Based on the actual Event Code, the Module Number or Event Parameter fields might not contain pertinent information. In that case the
field will contain zeros.
3.
The account number is sent using an account block that is separate from the event block.
4.
Multiple events can be sent within a single event block. Events are separated by a “/” character.
5.
Event parameter can be a Zone, Point or Circuit Number.
6.
“pi” modifier event is not used.
7.
Panel can be set to report by either Point or Zone.
Event
Report
Zone/
Point
Panel
ID
Module
Zone
ZZZZ
Point
ZZZZ
Fields Sent
SIA Event
Data
Fire Alarm-Zone
Zone
n/a
n/a97
15
n/a
EE-ZZ
FA15
Fire Alarm-Zone
Zone
n/a
n/a
05
n/a
EE-Z
FA5
Fire Alarm-Point
Point
n/a
01
n/a
123
EE-ZZ /EE-ZZZ pi01/FA123
Fire Alarm-Point
Point
n/a
33
n/a
203
EE-ZZ /EE-ZZZ
pi11/FA203
Expander Trouble
n/a
n/a
11
n/a
n/a
EE-ZZ
ET11
Auto Test
n/a
n/a
n/a
n/a
n/a
EE-Z
RP0
Battery Trouble-Panel 32
n/a
n/a
98
n/a
n/a
EE-ZZ
YT98
Battery Trouble-Expander 18 n/a
n/a
18
n/a
n/a
EE-ZZ
YT18
SLC Loop Shorted
n/a
n/a
44
n/a
n/a
EE-ZZ
ET44
Program Begin Panel ID=32
n/a
n/a
n/a
n/a
n/a
EE-Z
LB0
Program Begin Panel ID= 22
n/a
n/a
n/a
n/a
n/a
EE-Z
LB0
AC Power Loss - Panel 22
n/a
n/a
98
n/a
n/a
EE-Z
AT0
Fire Trouble
Point
n/a
97
n/a
200
EE-ZZ /EE-ZZZ
pi97/FT200
Fire Trouble
Zone
n/a
97
01
n/a
EE-Z
FT1
Fire Trouble-NAC
Point
n/a
98
n/a
NAC Circuit
7
EE-ZZ /EE-Z
pi98/FT7
Z=Pt. #
Fire Trouble-NAC
Zone
n/a
98
n/a
NAC Circuit
7
EE-ZZZ
FT400
ZZZ=OPG#
Table 11.3 SIA: FCP-75 Panels - PI Modifier Reporting Examples
Code
Event Code Description
EE
Event code (2 characters)
PP
Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM
Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically Module information)
ZZZZ
Event parameter (4 digits – Zero Filled) (typically Point, Zone or Circuit information)
Event
Report
Zone/Point
Panel ID
PP
Module
MM
Zone
ZZZZ
Point
ZZZZ
Fields
Sent
SIA Event
Data
Fire Alarm-Zone
Zone
32
n/a
15
n/a
EE-PP-MM-ZZZZ
FA32000015
Fire Alarm-Zone
Zone
32
n/a
05
n/a
EE-PP-MM-ZZZZ
FA32000005
Fire Alarm-Point
Point
32
01
n/a
123
EE-PP-MM-ZZZZ
FA32010123
Fire Alarm-Point
Point
21
33
n/a
203
EE-PP-MM-ZZZZ
FA21330203
Table 11.4 SIA REPORTING EXAMPLES