Receivers Compatible with the Control Panel
Reporting
FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
113
Ground fault condition trouble
YP
Exp. ID
YPNNXX0000
1
310
Exp. ID
000
Ground fault condition trouble restore
YQ
Exp. ID
YQNNXX0000
3
310
Exp. ID
000
Initial power up
RR
0
RRNN000000
1
305
00
000
Local programming aborted or ended with er-
rors
LU
0
LUNN000000
1
628
00
000
Local programming begin
LB
0
LBNN000000
1
627
00
000
Local programming ended normally
LS
0
LSNN000000
1
628
00
000
Network node trouble (panel missing)
EM
Panel ID
EMNNNN0000
1
334
Panel ID
000
Network node trouble restore
(panel no longer missing)
EN
Panel ID
ENNNNN0000
3
334
Panel ID
000
OPG Inhibit Trouble
FT
Group # + 1000
FTNN001GGG
1
320
00
Group #
OPG Inhibit Trouble Restore
FJ
Group # + 1000
FJNN001GGG
3
320
00
Group #
OPG Inhibit of Releasing Group
SS
Group # + 1000
SSNN001GGG
1
203
00
Group #
OPG Inhibit of Releasing Group Restore
SR
Group # + 1000
SRNN001GGG
3
203
00
Group #
Phone line 1 trouble detected
LT
1
LTNN000001
1
351
00
000
Phone line 1 trouble restore
LR
1
LRNN000001
3
351
00
000
Phone line 2 trouble detected
LT
2
LTNN000002
1
352
00
000
Phone line 2 trouble restore
LR
2
LRNN000002
3
352
00
000
Printer is off-line trouble
VZ
Exp. ID
VZNNXX0000
1
336
Exp. ID
000
Printer is off-line trouble restore
VY
Exp. ID
VYNNXX0000
3
336
Exp. ID
000
Printer is out of paper trouble
VO
Exp. ID
VONNXX0000
1
335
Exp. ID
000
Printer is out of paper trouble restore
VI
Exp. ID
VINNXX0000
3
335
Exp. ID
000
Releasing Notif/Control Circuit Disabled pi Exp. ID SS
Point #
SSNNXXPPPP
1
203
Exp. ID
Point #
Releasing Notif/Control Circuit enabled
pi Exp. ID SR
Point #
SRNNXXPPPP
3
203
Exp. ID
Point #
Remote programming aborted or ended with
errors
RU
0
RUNN000000
1
413
00
000
Remote programming ended normally
RS
0
RSNN000000
1
412
00
000
Repeater ground fault trouble
EM
0103
EMNN000103
1
334
Panel ID
103
Repeater ground fault trouble restore
EN
0103
ENNN000103
3
334
Panel ID
103
Repeater missing trouble
EM
0100
EMNN000100
1
334
Panel ID
100
Repeater missing trouble restore
EN
0100
ENNN000100
3
334
Panel ID
100
Repeater Rx1 communication trouble
EM
0101
EMNN000101
1
334
Panel ID
101
Repeater Rx1 communication trouble restore
EN
0101
ENNN000101
3
334
Panel ID
101
Repeater Rx2 communication trouble
EM
0102
EMNN000102
1
334
Panel ID
102
Repeater Rx2 communication trouble restore
EN
0102
ENNN000102
3
334
Panel ID
102
SBUS Class A supervision lost
ET
Exp. ID
ETNNXX0000
1
333
Exp. ID
000
SBUS Class A supervision restore
ER
Exp. ID
ERNNXX0000
3
333
Exp. ID
000
SBUS expander trouble
ET
Exp. ID
ETNNXX0000
1
333
Exp. ID
000
SBUS expander trouble restore
ER
Exp. ID
ERNNXX0000
3
333
Exp. ID
000
SLC class A supervision trouble
ET
Exp. ID
ETNNXX0000
1
331
Exp. ID
000
SLC class A supervision trouble restore
ER
Exp. ID
ERNNXX0000
3
331
Exp. ID
000
SLC programming ended, system active
TE
0
TENN000000
3
607
00
000
SLC programming started, system shut down
TS
0
TSNN000000
1
607
00
000
SLC short circuit trouble
ET
Exp. ID
ETNNXX0000
1
332
Exp. ID
000
SLC short circuit trouble restore
ER
Exp. ID
ERNNXX0000
3
332
Exp. ID
000
Time changed event
JT
0
JTNN000000
1
625
00
000
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
Table 11.2 Reporting Formats Table (Continued)
Summary of Contents for FCP-75
Page 144: ...Cut along dotted line ...
Page 145: ...FCP 75 Manual P N LS10147 003FK E A 3 17 2021 145 ...