P/N:LS10147-003FK-E:A 3/17/2021
61
4.
Select the Access Code you wish to edit by pressing the up or down arrow key.
5.
Then press ENTER.
Profile Edit Menu
From the Profile Edit Menu, you can change the users name, Access Code, and the panel functions that the user will have access to with their
code.
Edit Name
6.
See Appendix B for a list of available characters and their numeric designators.
7.
Then press ENTER to finish.
Edit Access Code
8.
Enter new Access Code (minimum of 4 digits, maximum of 7 digit).
9.
Press ENTER.
10. Enter code again. Press ENTER.
Panel Functions
11. Press the up or down arrow key to move through the list of available functions.
12. Then press right arrow to move to Y (yes) or N (no) selection column.
13. Press the up or down arrow key to select Y or N.
14. Press ENTER.
15. Repeat steps 12 through 15 until user profile is complete.
6.2.6 Communicator Options
Communicator options provides the configuration for reporting events to a central station.
1.
From the Main Menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options Menu.
Communicator Assignments
Each panel in the network system specifies which network communicator is used for reporting. The network communicator capability of the
linked system allows all panels to use the same communicator providing an economical solution for reducing the number of paths required
for reporting purposes. A communicator is specified by panel number. The network communicators will be used to report events according
to the communicator report table.
Communicator Miscellaneous
When using the SIA reporting format, the communicator sends information according to the SIA Reporting Type.
The selections for this option are:
1.
pi modifier (default)
2.
Panel ID*
Receiver Configuration
The network system can report events to as many as 68 receivers. See Appendix C for panel/receiver relationship numbers. Each receiver
can be assigned reporting credentials. When using a format that supports phone numbers, it can be up to forty digits long.
1.
From the Main Menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options Menu.
4.
Select 3 for Receiver Configuration.
5.
Select Panel to Program and press ENTER.
6.
Enter the receiver number that you want to report to. The receiver numbers available will correspond with what panel number you
entered. Receiver numbers are populated based on panel number and audited to allow only the 4 appropriate receivers. See Appendix C
for receiver number.
Available reporting format choices are:
•
Contact ID
•
SIA500
•
SIA8
•
SIA20
•
Ethernet
NOTE:
Profile 1 (Fire Fighter’s Key) the user name and Access Code can not be edited. Profile 2 (Installer) the user name and panel functions
can not be edited. Profile 3 (Multi-Site Installer) is defaulted with the Multi-Site access option, but the entire profile can be edited.
NOTE:
*Only SIA sends the panel ID when reporting.