94
FCP-75 Manual —
P/N LS10147-003FK-E:A 3/17/2021
Programming
System Options
7.
Enter a dialing prefix (if needed), then press ENTER. Or, Press the right arrow to bypass the dialing prefix option.
Number of Answer Rings
This option is used in conjunction with the HFSS Programming Tool. Use the option to determine the number of rings before the panel
answers a call from the computer. Range is 00-15 rings. This option is factory-programmed as 06 rings, which should be compatible for most
installations where the answering machine bypass feature is used. You may need to adjust it depending on the installation’s telephone sys-
tem.
The selection made here must match the programming for this option in the Communication Configuration dialog box of the HFSS Program-
ming Tool.
8.
Enter the desired number of answer rings, then press ENTER.
Dial Option (TouchTone or Pulse)
9.
Press the up or down arrow to select the dial option, then press ENTER.
Dial Format
10. Press the up or down arrow to select the pulse ratio for rotary dialing option, then press ENTER.
Options are:
Dial Tone Detection Disabled
11. Select Y (do disable) or N (don’t disable) by pressing the up or down arrow key, then press ENTER.
Monitor Line
Enable the line monitor for each phone line that will be used. See Figure 9.7 for location of this field on the phone lines screen. When the
phone line monitor has been enabled for a phone line, a trouble condition will occur if the line is not connected. If a phone line will not be
used, it must be disabled.
12. Select Y (monitor line) or N (don’t monitor line) by pressing the up or down arrow, then press ENTER.
Answering Machine Bypass
This option is used in conjunction with the HFSS Programming Tool. This feature ensures that an answering machine will not interfere with
communication between the panel and the computer. If an answering machine is used at the panel site, enable this feature; if an answering
machine is not used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication Configuration dialog box of the HFSS Program-
ming Tool.
13. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled) by pressing the up or down arrow, then press
ENTER.
Phone Line Unused
This option is used so that you can set unused phones lines to “Yes”, so no auto-test will be sent through that line.
This option is factory programmed as No.
14. Select Y or N by pressing the up or down arrow key, then press ENTER.
Edit Ethernet
1.
Enter the Installer Code. The panel will automatically go to the Main Menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next Menu, select 1 for Communication Options.
Dial Option
Description
PULSE
If this option is selected, only pulse dialing will be used for this phone line.
TT
TouchTone dialing. If this option is selected, only TouchTone dialing will be used for this
phone line.
TT/PL
TouchTone alternating with pulse. If this option is selected, the communicator will first
attempt to use TouchTone. It will switch to pulse if TouchTone is not successful on the first
attempt. It will continue to alternate between TT and pulse for additional attempts.
U
U.S. standard format. Uses the 60 msec / 40 msec make/break ratio.
E
European format. Uses the 66 msec / 34 msec make/break ratio.
Summary of Contents for FCP-75