46
FCP-75 Manual —
P/N LS10147-003FK-E:A 3/17/2021
Control Panel Installation
Remote Station Applications
4.15 Remote Station Applications
4.15.1 Keltron Model 3158 Installation
The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The 3158 reports alarms, super-
visories, and troubles. The 3158 is intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible
ratings.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete information.
1.
Wire the 3158 to the control panel as shown in the connection list and Figure 4.45.
2.
Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3.
Program control panel Relay 2 for alarm.
4.
Program NAC circuit 2 for alarm.
5.
Program NAC circuit 1 for supervisory non latching
Figure 4.45 Keltron 3158 Connection to Control Panel
4.15.2 City Box Connection Using the 5220 Module
This section describes how to connect the control panel to a municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Pro-
tected Fire Alarm systems for fire alarm service. The city (master) box is an enclosure that contains a manually operated transmitter used to
send an alarm to the municipal communication center which houses the central operating part of the fire alarm system.
City Box Standby Current: 0 (Notification supervision current counted for in control panel draw.)
Alarm Current: 1Amp for 1 second
Max Voltage: 27.4VDC
The maximum coil and wire resistance (combined) must not exceed 30 ohms.
To install the 5220 for city box connection:
1.
Use one of the knockouts on the right side of the control panel to connect the 5220 using a short piece of conduit (must not exceed 20
feet in length).
2.
Wire the 5220 to the control panel as shown in Figure 4.46. This drawing also shows how to connect the city box coil to terminals 3 and
4 on the 5220. Do not install an EOL resistor in the terminals of the NAC circuit used for this application.
3.
Connect earth ground wire to the 5220 chassis with mounting screw.
4.
Program the NAC circuit used as a continuous and non-silencing. Refer to Section 9.5 for point programming, Section 9.4 for group
settings, and Section 9.3 for zone settings and mapping.
NOTE:
NACs must be programmed for continuous and non-silencing
.
Example
An FIK-5496 must be
used for NAC circuits
This is intended for connection to a
polarity reversal circuit of a remote
station receiving unit having
compatible ratings.
Summary of Contents for FCP-75
Page 144: ...Cut along dotted line ...
Page 145: ...FCP 75 Manual P N LS10147 003FK E A 3 17 2021 145 ...