90
FCP-75 Manual —
P/N LS10147-003FK-E:A 3/17/2021
Programming
Point
CO SMOKE
DETECTOR
ALRM CO/ALRM FIRE
SUP CO/ALRM FIRE
ALRM CO/SUP FIRE
SUP CO/SUP FIRE
Latching
Non Latching
Detectors programmed as Supervisory can be latching or non-latching.
SWITCH
(cont.)
MAN_PULL
Use this switch type for manual pull stations. This input is always latched. The
switch can clear only when an alarm is reset.
WATERFLOW Latching
Non Latching
Use this switch type for monitoring water flow in a sprinkler system. Switch closure
will cause a sprinkler alarm. Water flow switches can be programmed as latching
or non-latching.
You can program a delay of up to 90 seconds to be used with a water flow switch.
The delay allows for normal, brief changes in sprinkler system water pressure.
The water flow alarm will not activate unless the switch is active for the
programmed delay time.
Note:
Waterflow delay of the FACP and the waterflow device shall not exceed
90 seconds.
If a delay is used, the system begins counting down when the switch closes. If the
switch opens (restores) before the timer expires, a water flow alarm is not
generated. If the water flow switch remains closed after the timer expires, a water
flow alarm will be generated.
SUPERVSY
Latching
Non Latching
Use this switch type for tamper monitoring of sprinklers and other fire protection
devices. If a contact closes, a sprinkler supervisory event will be generated.
Supervisory switches can be latching or non-latching.
FIRE DRILL
System-level, non latching switch. This switch is an alternative way of causing a
fire drill. It has the same operation as the fire drill option available from the
annunciator. When the switch is activated, a fire drill begins; when the switch is
de-activated, a fire drill ends.
SILENCE
System-level switch provides an alternate way to silence the system; same effect
as pressing the Silence key.
RESET
System-level switch provides an alternate way to reset the system; same effect as
pressing the Reset key.
PAS_ACK
Positive acknowledge switch. This switch must be used in zones programmed as
Positive Alarm Sequence (see Table 9.2).
If an acknowledge switch closes when an alarm or trouble condition is not already
in progress, a trouble will occur.
You must use a UL listed normally open, momentary switch type. The switch must
be rated at 5V, 100 mA (minimum) and be used with an EOL resistor for
supervision.
ZN_AUX1
Latching
Use these switch types if you want to monitor special zone-level conditions.
Non Latching
ZN_AUX2
Latching
Non Latching
SYS_AUX1
Latching
Use these switch types if you want to monitor special system-wide conditions.
Non Latching
SYS_AUX2
Latching
Non Latching
DETECT SW
Used to monitor conventional 4-wire detectors, a contact closure will generate a
detector alarm event.
SWITCH
(cont.)
TAMPER
Latching
Performs identically to a supervisory switch, but will be indicated as a tamper
switch on the LCD annunciator.
Non Latching
MAN REL
Manual release switch, typically a pull station.
ILOCK
Interlock release switch input.
CO DETECT SW
CO Detector Switch
CO SUPERVISORY
DETECT SW
CO Supervisory Detector Switch
STATUS PT
Status Point Switch
Type
Selection
Function
Latching Option
Comments
Table 9.4 Point Programming for Internal SLC Module (Continued)