Operation Mode Behavior
System Operation
FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
107
Supervisory
The system
detects a
supervisory
condition.
The system
detects a
supervisory
condition with a
CO detector
The communicator seizes control of the phone line and calls
the central station.
The on-board annunciator sounds a loud, pulsing beep in the
sequence one second on, one second off.
SUPERVISORY LED flashes.
The LCD displays a screen similar to this one.
Press down arrow to view the supervisory condition. A
screen similar to this one displays.
Press SILENCE and enter an Access Code (or activate
the key) to silence the annunciator.
Once the supervisory condition has been corrected, the
system will restore itself automatically.
Trouble
A system
trouble condition
occurs.
A trouble
condition with a
CO detector
The communicator seizes control of the phone line and calls
the central station.
The on-board annunciator sounds a loud, pulsing beep in the
sequence one second on, nine seconds off.
SYSTEM TROUBLE LED flashes.
The LCD displays a screen similar to this one.
Press down arrow to view the trouble. A screen similar to
this one displays.
Press SILENCE and enter an Access Code (or activate
the key) to silence the annunciator.
Once the trouble condition has been fixed, the system
will restore itself automatically.
Operation
Mode
Occurs When
System Behavior
In This Mode You Can
Table 10.1 Panel Modes (Continued)