SIA / FCP-75 Panels PI Modifier Reporting:
Reporting
FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
119
11.2 SIA / FCP-75 Panels PI Modifier Reporting:
Events are sent to the central station as a variable length string:
The Event Format is:
EEZZZZ
Where the Event Format is defined as follows:
1.
The Account Number is sent using an account block that is separate from the event block.
2.
Multiple events can be sent within a single event block. Events are separated by a “/” character.
3.
Event parameter can be either a zone, point or module number.
Voice Aux Status 1 Switch is Trouble Re-
stored
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
379
Exp. ID
Point #
Voice Aux Status 1 Switch is Disabled
pi Exp. ID UB
Point #
UBNXXPPPP
1
580
Exp. ID
Point #
Voice Aux Status 1 Switch is Enabled
pi Exp. ID UU
Point #
UUNXXPPPP
3
580
Exp. ID
Point #
Voice Aux Status 2 Switch is Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
379
Exp. ID
Point #
Voice Aux Status 2 Switch is Trouble Re-
stored
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
379
Exp. ID
Point #
Voice Aux Status 2 Switch is Disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
580
Exp. ID
Point #
Voice Aux Status 2 Switch is Enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
580
Exp. ID
Point #
Water flow switch alarm
pi Exp. ID SA
Point #
SANNXXPPPP
1
113
Exp. ID
Point #
Water flow switch alarm restore
pi Exp. ID SH
Point #
SHNNXXPPPP
3
113
Exp. ID
Point #
Water flow switch disabled
pi Exp. ID SB
Point #
SBNNXXPPPP
1
571
Exp. ID
Point #
Water flow switch enabled
pi Exp. ID SU
Point #
SUNNXXPPPP
3
571
Exp. ID
Point #
Water flow switch trouble
pi Exp. ID ST
Point #
STNNXXPPPP
1
373
Exp. ID
Point #
Water flow switch trouble restore
pi Exp. ID SJ
Point #
SJNNXXPPPP
3
373
Exp. ID
Point #
Zone-based AUX1 switch alarm
pi Exp. ID UA
Point #
UANNXXPPPP
1
140
Exp. ID
Point #
Zone-based AUX1 switch alarm restore
pi Exp. ID UH
Point #
UHNNXXPPPP
3
140
Exp. ID
Point #
Zone-based AUX1 switch disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
571
Exp. ID
Point #
Zone-based AUX1 switch enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
571
Exp. ID
Point #
Zone-based AUX1 switch trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
Zone-based AUX1 switch trouble restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Zone-based AUX2 switch alarm
pi Exp. ID UA
Point #
UANNXXPPPP
1
140
Exp. ID
Point #
Zone-based AUX2 switch alarm restore
pi Exp. ID UH
Point #
UHNNXXPPPP
3
140
Exp. ID
Point #
Zone-based AUX2 switch disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
571
Exp. ID
Point #
Zone-based AUX2 switch enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
571
Exp. ID
Point #
Zone-based AUX2 switch trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
Zone-based AUX2 switch trouble restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
System-based Wireless Gateway Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
System-based Wireless Gateway
Trouble - restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Wireless Gateway Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
Wireless Gateway Trouble restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
Table 11.2 Reporting Formats Table (Continued)
Code
Event Code Description
EE
Event Code (2 characters)
ZZZZ
Event parameter (up to four digits – not zero filled)