18
FCP-75 Manual —
P/N LS10147-003FK-E:A 3/17/2021
Before You Begin Installing
Calculating Current Draw and Standby Battery
3.7.2 Current Draw Worksheet for Fike IDP SLC Devices
Use Table 3.3 to determine current requirements during alarm/battery standby operation when SLC devices are installed. You can install up
to 75 IDP detectors
and
75 IDP
modules
1
.
Device
# of Devices
Current per Device
Standby
Current
Alarm Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from battery)
1
Standby: 165 mA
165 mA
Alarm: 310 mA
310 mA
Addressable SLC Detectors
FIK-2351
SLC
Standby: 200µA
mA
Alarm: 4.5mA
mA
FIK-2351R
SLC
Standby: 200µA
mA
Alarm: 4.5mA
mA
FIK-2351T
SLC
Standby: 200µA
mA
Alarm: 4.5mA
mA
FIK-5351
SLC
Standby: 200µA
mA
Alarm: 4.5mA
mA
FIK-5351R
SLC
Standby: 200µA
mA
Alarm: 4.5mA
mA
FIK-5351H
SLC
Standby: 200µA
mA
Alarm: 4.5mA
mA
DNR
5
(non-Relay)
None, included with FIK-2351R
6
DNR
6
(with Relay)
None, included with FIK-2351R & FIK-M500R
7
Addressable SLC Modules
FIK-M500M
Standby/Alarm 0.375 mA
mA
mA
FIK-M501M
mA
mA
FIK-PULL-SA/FIK-PULL-DA
FIK-M500DM
Standby/Alarm: 0.75mA
mA
mA
FIK-IM-10
Standby/Alarm: 3.5mA
mA
mA
FIK-M500S
SLC
Standby: 0.375mA
Alarm: 0.375mA
mA
mA
Aux Pwr
Standby: 1.7mA
mA
Alarm: 7mA
mA
FIK-SC-6
SLC
Standby: 2.25mA
Alarm: 2.25mA
mA
mA
Aux Pwr
Standby: 8mA
mA
Alarm: 20mA
mA
FIK-M500R
Standby/Alarm: .255mA
mA
mA
FIK-CR-6
Standby/Alarm: 1.45mA
mA
mA
FIK-M500MR-2
Standby: 1.3mA
mA
Alarm: 24mA
mA
FIK-M502M
Aux Pwr
Standby: 12mA
mA
mA
Alarm: 90mA
mA
mA
SLC
Standby/Alarm: .27mA
mA
mA
FIK-CZ-6
Aux Pwr
Standby: 50mA
mA
mA
Alarm: 270mA
mA
mA
SLC
Standby/Alarm: 2mA
mA
mA
SLC Accessories
B200S-WH / -IV Intelligent sounder base
Aux Pwr
Standby: .5mA
mA
Alarm: (high vol) 35mA
mA
SLC
Standby .3mA
mA
B200S-LF-WH / -IV Low Frequency sounder base
Aux Pwr
Standby .55mA
mA
Alarm (high vol) 140mA
mA
SLC
Standby .30mA
mA
B224RB-WH / -IV Relay Base
Standby/Alarm: .5mA
mA
mA
SLC Isolator Devices
FIK-M500X
(100 max.)
Standby/Alarm: .45mA
mA
mA
Color Guide: -IV = Ivory color, -BL = Black, -WH = White, -WHITE-White
Table 3.3 Current Calculation Worksheet for Fike IDP Devices
Summary of Contents for FCP-75
Page 144: ...Cut along dotted line ...
Page 145: ...FCP 75 Manual P N LS10147 003FK E A 3 17 2021 145 ...